Generac QT02224JNAX 사용자 설명서

다운로드
페이지 9
3 of 9
22 • 27 • 36 • 48 kW 
operating data
GENERATOR OUTPUT VOLTAGE/kW - 60Hz
kW LPG
Amp LPG
kW Nat. Gas
Amp Nat. Gas
CB Size (Both)
QT022
120/240 V, 1Ø, 1.0 pf
22
92
22
92
100
120/208 V, 3Ø, 0.8 pf
22
76
22
76
80
120/240 V, 3Ø, 0.8 pf
22
66
22
66
80
QT027
120/240 V, 1Ø, 1.0 pf
27
113
25
104
125
120/208 V, 3Ø, 0.8 pf
27
94
25
87
100
120/240 V, 3Ø, 0.8 pf
27
81
25
75
90
QT036
120/240 V, 1Ø, 1.0 pf
36
150
35
146
175
120/208 V, 3Ø, 0.8 pf
36
125
35
121
150
120/240 V, 3Ø, 0.8 pf
36
108
35
105
125
277/480 V, 3Ø, 0.8 pf
36
54
35
53
60
QT048
120/240 V, 1Ø, 1.0 pf
48
200
48
200
200
120/208 V, 3Ø, 0.8 pf
48
166.5
48
166
175
120/240 V, 3Ø, 0.8 pf
48
144
48
144
150
277/480 V, 3Ø, 0.8 pf
48
72
48
72
80
SURGE CAPACITY IN AMPS
Voltage Dip @ < .4 pf
15%
30%
QT022
120/240 V, 1Ø
89
216
120/208 V, 3Ø
74
180
120/240 V, 3Ø
64
156
QT027
120/240 V, 1Ø
109
265
120/208 V, 3Ø
91
221
120/240 V, 3Ø
79
192
QT036
120/240 V, 1Ø
54
149
120/208 V, 3Ø
87
210
120/240 V, 3Ø
75
182
277/480 V, 3Ø
36
87
QT048
120/240 V, 1Ø
69
189
120/208 V, 3Ø
111
269
120/240 V, 3Ø
96
233
277/480 V, 3Ø
43
104
ENGINE FUEL CONSUMPTION
Natural Gas
Propane
(ft
3
/hr)
(m³/hr)
(gal/hr)
(l/hr)
QT022
Exercise cycle
42
1.2
0.44
1.7
25% of rated load
100
2.8
1.1
4.2
50% of rated load
190
5.4
2.1
7.8
75% of rated load
255
7.2
2.8
10.5
100% of rated load
316
9
3.4
13
QT027
Exercise cycle
42
1.2
0.44
1.7
25% of rated load
108
3.1
1.2
4.5
50% of rated load
197
5.6
2.1
8.1
75% of rated load
287
8.2
3.1
11.8
100% of rated load
359
10.2
3.9
14.8
QT036
Exercise cycle
48
1.4
0.5
2
25% of rated load
156
4.4
1.7
6.4
50% of rated load
282
8
3.1
11.6
75% of rated load
392
11.1
4.3
16.2
100% of rated load
503
14.3
5.5
20.8
QT048
Exercise cycle
95
2.7
1
3.9
25% of rated load
204
5.8
2.16
8.5
50% of rated load
392
11.1
4.14
15.7
75% of rated load
547
15.5
5.8
22.8
100% of rated load
756
21.5
7.96
31.3
Quietsource
®
 Series
STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage.  There 
is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice.
Note: Fuel pipe must be sized for full load. 
For Btu content, multiply ft
3
/hr x 2520 (LP) or ft
3
/hr x 1000 (NG) 
For megajoule content, multiple m³/hr x 93.89 (LP) or m³/hr x 37.26 (NG)
Refer to "Emissions Data Sheets" for maximum fuel flow for EPA and SCAQMD permitting purposes.