Generac 005802-0 사용자 설명서

다운로드
페이지 40
2.3.4  120/240 VAC, 50 AMP RECEPTACLE
Use a NEMA 14-50 plug with this receptacle. Connect a 4-wire 
cord set rated for 250 Volts AC at 50 Amps to the plug (Figure 
6).
Use this receptacle to operate 120/240 Volt AC, 60 Hz electrical 
loads requiring up to 10,000 watts (10.0 kW) of power at 41.6 
Amps for 240 volts or two independent 120 Volt loads. This 
receptacle is protected by a 42 Amp 2-pole circuit breaker.
Figure 6 - 120/240 VAC, 50 Amp Receptacle
50 A
NOTE:
Receptacles may be marked with rating values greater than 
generator output capacity.
2.4  HOW TO USE THE GENERATOR
If there are any problems operating the generator, please call the 
generator helpline at 1-888-436-3722.
n
  Never operate in an enclosed area or indoors! 
NEVER use in the home, or in partly enclosed 
areas such as garages, even if doors and 
windows are open! ONLY use outdoors and far 
from open windows, doors, vents, and in an 
area that will not accumulate deadly exhaust.
n
 The engine exhaust fumes contain carbon 
monoxide, which can you cannot see or smell. 
This poisonous gas, if breathed in sufficient 
concentrations, can cause unconsciousness or 
even death.
n
 Adequate, unobstructed flow of cooling and 
ventilating air is critical to correct generator 
operation. Do not alter the installation or permit 
even partial blockage of ventilation provisions, 
as this can seriously affect safe operation 
of the generator. The generator MUST be 
operated outdoors.
n
 This exhaust system must be properly 
maintained. Do nothing that might render the 
exhaust system unsafe or in noncompliance 
with any local codes and/or standards.
n
 Always use a battery operated carbon 
monoxide alarm indoors, installed according to 
the manufacturers instructions.
2.4.1 SYSTEM 
GROUND
The generator has a system ground that connects the generator 
frame components to the ground terminals on the AC output 
receptacles.  The system ground is bonded to the AC neutral wire 
in the generator control panel via a jumper wire.
Special Requirements
There may be Federal or State Occupational Safety and Health 
Administration (OSHA) regulations, local codes, or ordinances that 
apply to the intended use of the generator.
Please consult a qualified electrician, electrical inspector, or the 
local agency having jurisdiction:
In some areas, generators are required to be registered with 
• 
local utility companies.
If the generator is used at a construction site, there may be 
• 
additional regulations which must be observed.
Connecting to a Building’s Electrical System
Connections for standby power to a building’s electrical system 
must be made by a qualified electrician.  The connection must 
isolate the generator power from utility power or other alternative 
power sources and must comply with all applicable laws and 
electrical codes.
7
Operation