Baldor GLC15 사용자 설명서

다운로드
페이지 114
Appendix B
Series GLC Information & Wiring Diagrams
Series GLC B‐1
MN2408
GLC Circuit Breaker & Electrical Data
Circuit Breaker Size
Qty per Phase
Min Wire Gauge
OSH Plant
Ampacity @125C
15
1
#16
1 - #8 EPDM PER PHASE
90
20
1
#16
1 - #8 EPDM PER PHASE
90
30
1
#14
1 - #8 EPDM PER PHASE
90
40
1
#12
1 - #8 EPDM PER PHASE
90
50
1
#10
1 - #8 EPDM PER PHASE
90
60
1
#8
1 - #8 EPDM PER PHASE
90
70
1
#8
1 - #8 EPDM PER PHASE
90
80
1
#6
1 - #8 EPDM PER PHASE
90
90
1
#6
1 - #6 EPDM PER PHASE
125
100
1
#6
1 - #6 EPDM PER PHASE
125
110
1
#6
1 - #6 EPDM PER PHASE
125
125
1
#4
1 - #4 EPDM PER PHASE
170
150
1
#2
1 - #4 EPDM PER PHASE
170
175
1
#2
1 - #1 EPDM PER PHASE
265
200
1
#1
1 - #1 EPDM PER PHASE
265
225
1
1/0
1 - #1 EPDM PER PHASE
265
250
1
2/0
1 - #1/0 EPDM PER PHASE
305
300
1
4/0
1 - #2/0 EPDM PER PHASE
355
350
1
4/0
1 - #3/0 EPDM PER PHASE
410
400
2
#1
1 - #4/0 EPDM PER PHASE
475
450
2
1/0
2 - #1/0 EPDM PER PHASE
610
500
2
1/0
2 - #1/0 EPDM PER PHASE
610
600
2
3/0
2 - #2/0 EPDM PER PHASE
710
700
2
4/0
2 - #3/0 EPDM PER PHASE
820
800
3
2/0
2 - #4/0 EPDM PER PHASE
950
900
3
3/0
3 - #2/0 EPDM PER PHASE
1065
1000
3
3/0
3 - #3/0 EPDM PER PHASE
1230
1200
3
250
3 - #4/0 EPDM PER PHASE
1425
1400
4
4/0
4 - #4/0 EPDM PER PHASE
1900
1600
4
250
4 - #4/0 EPDM PER PHASE
1900
2000
5
250
5 - #4/0 EPDM PER PHASE
2375
2500
6
250
6 - #4/0 EPDM PER PHASE
2850
3000
7
250
7 - #4/0 EPDM PER PHASE
3325
4000
8
300
9 - #4/0 EPDM PER PHASE
4275
Wiring Diagrams
Wiring diagrams for these generators are contained on the following pages of this appendix.