sEctioN 4.4
DiaGNostic tEsts
Page 133
CHOKE SOLENOID
CHOKE PLATE
Figure 22. Solenoid De-Energized, Choke Closed 
12-20 kW Units 
CHOKE SOLENOID
CHOKE PLATE
Figure 23. Solenoid Energized, Choke Open 
12-20 kW Units
3.  Set a VOM to measure DC voltage. 
4.  Connect the positive (+) test lead to Wire 14 (Pin 1) of the 
C3 Connector going to the control panel (Female Side). 
Connect the negative (-) test lead to Wire 90 (Pin 2).
5.  Set the AUTO-OFF-MANUAL Switch to MANUAL. While 
cranking, battery voltage should be measured cyclically. 
If  battery  voltage  was  not  measured,  verify  continuity 
of Wire 90 between the C3 Connector and the printed 
circuit  board  J1  Connector,  Pin  Location  J1-23. Verify 
continuity  of Wire  14  between  the  C3  Connector  and 
J2 connector Pin Location J2-3. Repair or replace any 
wiring as needed.
6.  Disconnect C3 Connector. Set a VOM to measure resis-
tance. Connect the positive (+) test lead to Wire 14 (Pin 
1) of C3 Connector going to the choke solenoid (Male 
Side). Connect the negative (-) test lead to Wire 90 (Pin 
2). Approximately 3.7 ohms should be measured.
7.  With the generator running at a speed of approximately 
60  Hertz,  verify  that  the  choke  is  energized  and  hold-
ing  the  choke  plate  open.  Repeat  Step  2  procedure, 
however, once the unit starts, manually hold the choke 
open while taking the voltage measurement.
CHOKE PLATE
CHOKE SOLENOID
CHOKE HOUSING
Figure 24. Exploded View Showing Location of Choke 
Plate - 10 kW Units
FEMALE SIDE
MALE SIDE
2
1
1 2
90
90
14
14
Figure 25. C3 Choke Solenoid Connector
RESULTS:
1.  If Battery voltage was not measured in Step 5 and wire 
continuity is good, replace the printed circuit board.
2.  If  Choke  Solenoid  coil  resistance  is  not  measured  in 
Step 6, replace the Choke Solenoid.
PROCEDURE: 8 kW UNITS
1. 
Operational  Check:  Set  the  AUTO-OFF-MANUAL 
Switch to MANUAL. While cranking the choke solenoid 
should energize and pull the choke plate closed. If the 
choke  solenoid  does  not  pull  in,  verify  that  the  choke 
can be manually closed. There should be no binding or 
interference.
DC CONTROL
Part 4