NOTE:  If,  for  any  reason,  sensing  voltage  to  the 
regulator is lost, the regulator will shut down and 
excitation  output  to  the  Rotor  will  be  lost. The 
AC  output  voltage  will  then  drop  to  a  value  that 
is  commensurate  with  Rotor  residual  magnetism 
(about  7-12 VAC). Without  this  automatic  shut-
down  feature,  loss  of  sensing  (actual)  voltage  to 
the  regulator  would  result  in  a “full  field”  or “full 
excitation”  condition  and  an  extremely  high  AC 
output voltage. 
NOTE:  Adjustment  of  the  regulator’s “VOLTAgE 
AdJUST” potentiometer must be done only when 
the unit is running at its correct governed no-load 
speed.  Speed  is  correct  when  the  unit’s  no-load 
AC  output  frequency  is  about  60.0-60.5  Hertz.  At 
the stated frequency, AC output voltage should be 
about 124 volts.
CRANkCASE BREATHER
CRANKCASE 
BREATHER
GASKET
SCREEN
OIL VAPOR
COLLECTOR
Figure 2-8. – Crankcase Breather
DESCRIPTION:
The crankcase breather is equipped with a reed valve 
to control and maintain a partial vacuum in the crank-
case. The breather is vented to the airbox. The breath-
er  chamber  contains  a  removable  oil  vapor  collector. 
Oil vapor is condensed on the collector material and 
drains  back  into  the  crankcase,  which  minimizes  the 
amount of oil vapor entering the breather.
CHECk BREATHER:
1.  Disconnect breather tube and remove two screws 
and breather. Discard gasket.
2.  Remove oil vapor collector and retainer.
3.  Check  collector  for  deterioration  and  replace  if 
necessary.
INSTALL BREATHER:
1.  Install oil vapor collector and retainer.
Note: Push oil vapor collector and retainer in until 
it bottoms.
2.  Install breather with new gasket (Figure 2-8).
a. Torque screws to 5-8 ft-lbs.
3.  Assemble breather tube to intake elbow.