Generac Power Systems 5412 사용자 설명서

다운로드
페이지 82
Section 5
ENGINE DC CONTROL SYSTEM
Page 21
5 Flashes = Low Oil Pressure
4 Flashes = Overspeed
3 Flashes = Overcrank
2 Flashes = Low Battery
6 Flashes = High Oil Temperature
SC - STARTER CONTACTOR
TB - TERMINAL BLOCK, 4 TAB
SP2 - SPARK PLUG, CYL. 2
SP1 - SPARK PLUG, CYL. 1
LED - ALARM INDICATOR
LOP - LOW OIL PRESSURE SWITCH
SCR - STARTER CONTACTOR RELAY
SM - STARTER MOTOR
SW1 - PRIME/START-RUN-OFF SWITCH
FS - FUEL SOLENOID
FP - FUEL PUMP
F1 - FUSE, 7.5A
CH - CHOKE HEATER
CS - CHOKE SOLENOID
IMS - IGNITION MODULE STUD
IM2 - IGNITION MODULE, CYL. 2
HTO - HIGH OIL TEMPERATURE SWITCH
IM1 - IGNITION MODULE, CYL. 1
GRD1 - CONTROL PANEL GROUND
GRD2 - UNIT GROUND STUD
BA - BRUSH ASSEMBLY
CB 1 / CB 2 - SEE CHART
LEGEND
= 12 VOLTS DC
= ALARM CONTROL (PCB)
= DC CONTROL VOLTAGE (PCB)
= SHUTDOWN CONTROL (PCB)
= GROUND
= GROUND CONTROL (PCB)
= FIELD BOOST
= VOLTAGE REGULATOR
   DC OUTPUT
= AC VOLTAGE
IM1
IM2
SP1
SP2
12
J1
1 2 3 4 5 6 7 8
10
9
11
13 14
PRINTED CIRCUIT BOARD
J2
CONTROL
ACTUATOR
GOVERNOR
SW1
START
PRIME
STOP
18
17
0
SCR
56
16
F1
0
13
16
56
FP
LOP
HTO
BLK
RED
18A
0
86
0
85
REGULATOR
VOLTAGE
2
2
0
6
22S
4
11S
6
0
4
22S
11S
LED
0
712
CH
CS
0
90
14
RED
BLACK
SM
SC
BATTERY
+
-
12V
SC
0
0
16
16
0
13
POWER WINDINGS
11
BA
33
DPE WINDING
6
2
4
0
44
CB2
CB1
FIELD
BLACK
RED
18
17
0
56
712
0
18
11S
22S
13
16
0
17
REMOTE
PANEL
CONNECTOR
14
712
D
E
G
F
C
B
18
17
H
A
0
GREEN
WHITE
0
13
712
14
0
GREEN
WHITE
0
NEUTRAL CONNECTION
AC CONNECTION
CUSTOMER
BY CUSTOMER
18
15
17
712
86
90
14
85
56
0
18A
4
15
11S
0
14
0
241
FS
14
712
22
44
44
22
22S 22
0
0
0
+
-
CIRCUIT CONDITION – SHUTDOWN:
Setting  the  START-STOP  SWITCH  (SW1)  or  the  REMOTE  PANEL 
START-STOP  SWITCH  to  its  “STOP”  position  connects  the  Wire 
18  circuit  to  frame  ground.  Printed  Circuit  Board  action  then  closes 
the circuit to Wire 18A, grounding the ignition magneto. PCB action 
de-energizes  DC  output  to  j1  plug  to  the  FUEL  PUMP  (FP),  FUEL 
SOLENOID (FS) and CHOkE HEATER (CH) are de-energized by the 
loss of DC to Wire 14. Ignition and fuel flow are terminated, and the 
engine shuts down.
CIRCUIT CONDITION – FAULT SHUTDOWN:
The  engine  mounts  a  HIGH  OIL TEMPERATURE  SWITCH  (HTO) 
and a LOW OIL PRESSURE SWITCH (LOP). 
Should engine oil temperature exceed a preset value, the switch con-
tacts will close. Wire 85 from the Printed Circuit Board will connect to 
frame ground. PCB action will then initiate a shutdown and will cause 
the red led light on SW1 to flash 6 times then repeat.
Should engine oil pressure drop below a safe pre-set value, the LOP 
switch contacts will close. On contact closure, Wire 86 will be connect-
ed to frame ground and PCB action will initiate an engine shutdown 
and will cause the red led light on SW1 to flash 5 times then repeat.
The PCB has a built-in time delay for the Wire 85 fault shutdown. At 
STARTUP ONLY the circuit board will wait approximately 6 seconds 
before  looking  at  the Wire  85  fault  shutdowns.  Once  running,  after 
the 6 second time delay, grounding Wire 85 through either switch will 
cause an immediate shutdown.