Section 7
DIAGNOSTIC TESTS
A. Schematic
B. Pictorial
2
2
6
6
Figure 7-8. – Stator Excitation Winding
PROCEDURE:
1.  Disconnect Wire 2 from the Voltage Regulator.
2.  Disconnect Wire 6 from the Voltage Regulator.
3.  Set a VOM to its “Rx1” scale and zero the meter.
4.  Connect  the VOM  test  leads  across  the  terminal 
ends of Wires  2 and 6. The VOM should indicate 
the  resistance  of  the  Stator  Excitation  (DPE) 
Windings.
EXCITATION “DPE” WINDING RESISTANCE 
*
 
(Measured Across Wires 2 & 6)
MODEL
OHMS
RV45 (5410/5411)
2.59
Ω
RV55 (5412/5413)
1.41
Ω − 1.63Ω
RV65 (5414/5415)
1.59
Ω − 1.84Ω
 
* Resistance values In ohms (Ω) at 20°C. (68°F.). 
Actual  readings  may  vary  depending  on  ambient 
temperature.  A  tolerance  of  plus  or  minus  5%  is 
allowed.
5.  Now,  set  the  meter  to  its “Rx1  k”  or “Rx10,000” 
scale  and  zero  the  meter. Test  for  a  “short-to-
ground” condition as follows:
a. Connect one meter test lead to Stator lead No. 
2, the other test lead to a clean frame ground.
b. The meter should read “Infinity”. Any other read-
ing  indicates  a  “short-to-ground”  condition  and 
the Stator should be replaced.
6.  Test for a short between windings as follows:
a. Meter should be set to its “Rx1 k” or “Rx10,000” 
scale.
b. Connect  one  meter  test  lead  to  Stator  lead  2, 
the other test lead to Stator lead 11. The meter 
should read “Infinity”.
c. Connect one VOM test lead to Stator lead 2 the 
other test lead to Stator lead 33. “Infinity” should 
be indicated.
RESULTS:
1.  If  the  Stator  excitation  (DPE)  windings  are  open 
or shorted, replace the Stator assembly.
2.  If  the  excitation  windings  are  good,  perform 
“Insulation Resistance Test”, page 13.
TEST 7 – CHECk SENSINg LEAdS / POWER 
WINdINgS
DISCUSSION:
The Voltage  Regulator  “regulates”  excitation  current 
flow to the Rotor by electronically comparing sensing 
voltage  to  a  pre-set  reference  voltage. The  sensing 
voltage is delivered to the Voltage Regulator via Wires 
11S and 22S.
If an open circuit exists in sensing leads 11S or 22S, 
the  normal  reaction  of  an  unprotected  Regulator 
would  be  to  increase  the  excitation  current  to  the 
Rotor  in  an  effort  to  increase  the  actual  AC  output 
voltage. This would result in a “full field” condition and 
an extremely high AC output voltage.
To protect the system against such a high AC output 
voltage, the Voltage Regulator will shut down if sens-
ing voltage signals are lost.
If the regulator shuts down, the generator’s AC output 
voltage will decrease to a value that is commensurate 
with the Rotor’s residual magnetism (about 5-12 VAC).
PROCEDURE:
Gain  access  to  the  generator  control  panel  interior. 
Test the Stator power windings, as follows:
1.  From main breaker, disconnect Wires 11 and 33.
2.  Also disconnect Wires 22 and 44 from the ground 
terminal.
3.  Disconnect Wires  11S  and  22S  from  the Voltage 
Regulator.
4.  Set a VOM to its “Rx1” scale and zero the meter.
5.  Connect the meter test leads across Stator leads 
11  and  22.  Normal  power  winding  resistance 
should be read.
6.  Connect the meter test leads across Stator leads 
33  and  44.  Normal  power  winding  resistance 
should be read.
7.  Connect the meter test leads across Stator leads 
11S  and  22S.  Normal  Power Winding  resistance 
should be read.
Page 40