    DaNGEr: usE EXtrEmE cautioN 
DuriNG tHis tEst. tHE GENErator Will 
BE ruNNiNG. HiGH aND DaNGErous 
VoltaGEs Will BE PrEsENt at tHE 
tEst tErmiNals. coNNEct mEtEr tEst 
clamPs to tHE HiGH VoltaGE tErmiNals 
WHilE tHE GENErator is sHut DoWN. 
staY clEar of PoWEr tErmiNals 
DuriNG tHE tEst. maKE surE mEtEr 
clamPs arE sEcurElY attacHED aND 
Will Not sHaKE loosE.
PROCEDURE:
1.  With  the  engine  shut  down,  connect  the  AC  voltmeter 
test leads across the Wires 11 and 44 terminals of the 
generator  main  circuit  breaker  (see  Figure  1). These 
connections will permit line-to-line voltages to be read.
2.  Set  the  generator  main  circuit  breaker  to  its  OFF  or 
“Open”  position. This  test  will  be  conducted  with  the 
generator running at no-load.
3.  Start  the  generator,  let  it  stabilize  and  warm  up  for  a 
minute or two.
4.  Take  the  meter  reading.  On  12-20  kW  units  the  no-load 
voltage  should  be  between  249-247 VAC.  On  8-10  kW 
units the no-load voltage should be between 220-235 VAC.
5.  Shut the engine down and remove the meter test leads.
RESULTS:
1.  If Step 4 indicated proper voltages, discontinue testing.
2.  If any other readings were measured, refer back to flow 
chart.
note: “residual”  voltage  may  be  defined  as  the 
voltage  that  is  produced  by  rotor  residual  mag-
netism alone. the amount of voltage induced into 
the  stator  ac  power  windings  by  residual  volt-
age  alone  will  be  approximately  2  to  16  volts  ac, 
depending  on  the  characteristics  of  the  specific 
generator.  if  a  unit  is  supplying  residual  voltage 
only,  either  excitation  current  is  not  reaching  the 
rotor or the rotor windings are open and the exci-
tation  current  cannot  pass.  on  current  units  with 
air-cooled  engine, “field  boost”  current  flow  is 
available to the rotor only during engine cranking.
teSt 4 – FiXed eXcitation teSt/ 
rotor amp draW teSt
DISCUSSION:
Supplying a fixed DC current to the rotor will induce a 
magnetic field in the rotor. With the generator running, 
this  should  create  a  proportional  voltage  output  from 
the stator windings.
PROCEDURE:
1.  Disconnect Wire  4  from  the  voltage  regulator,  3rd 
terminal from the top. See Figure 2.
2.  Connect a jumper wire to the disconnected Wire 4 and 
to the 12 volt fused battery supply Wire 15B (located at 
TB1 terminal board).
3. 
Set VOM to AC volts.
11
22
4
4
0
6
2
Figure 2. Voltage Regulator
4.  Disconnect Wire 2 from the voltage regulator and con-
nect one meter test lead to that wire. Disconnect Wire 
6  from  the  voltage  regulator  and  connect  the  other 
meter test lead to that wire. Wires 2 and 6 are located 
at  the  bottom  two  terminals  of  the  voltage  regulator 
(see Figure 2).
5.  Set the AUTO-OFF-MANUAL switch to MANUAL. Once 
the engine starts, record the AC voltage.
6.  Set the AUTO-OFF-MANUAL switch to OFF. Reconnect 
Wire 2 and Wire 6.
7.  Disconnect Wire 11 from the voltage regulator and con-
nect one meter test lead to that wire. Disconnect Wire 
22  from  the  voltage  regulator  and  connect  the  other 
meter test lead to that wire (both wires are located at the 
top two terminals of the voltage regulator, see Figure 2).
8.  Set the AUTO-OFF-MANUAL switch to MANUAL. Once 
the engine starts, record the AC voltage.
9.  Set the AUTO-OFF-MANUAL switch to OFF. Reconnect 
Wire 11 and Wire 22.
10. 
Set VOM to DC amperage.
11. Remove jumper lead connected to Wire 4 and Wire 15B.
12. Connect  one  meter  test  lead  to  battery  positive  12 
VDC supply Wire 15B, located at TB1 terminal board. 
Page 42
Part 2
AC GENERATORS
sEctioN 2.4
DiaGNostic tEsts