sEctioN 4.4
DiaGNostic tEsts
introduction 
Perform  these  “Diagnostic  Tests”  in  conjunction  with 
the “Troubleshooting Flow Charts” of Section 4.3. 
The  test  procedures  and  methods  presented  in  this 
section are not exhaustive. The manufacturer could not 
possibly know of, evaluate and advise the service trade 
of  all  conceivable  ways  in  which  testing  and  trouble 
diagnosis  might  be  performed. The  manufacturer  has 
not undertaken any such broad evaluation.
teSt 56 – check poSition oF auto-oFF- 
manual SWitch 
DISCUSSION: 
If  the  standby  system  is  to  operate  automatically,  the 
generator AUTO-OFF-MANUAL switch must be set to 
AUTO. That  is,  the  generator  will  not  crank  and  start 
on  occurrence  of  a “Utility”  power  outage  unless  that 
switch  is  at  AUTO.  In  addition,  the  generator  will  not 
exercise every seven (7) days as programmed unless 
the switch is at AUTO.
AUTO
OFF
MANUAL
Figure 1. AUTO-OFF-MANUAL Switch Positions
PROCEDURE: 
With  the  AUTO-OFF-MANUAL  switch  set  to  AUTO, 
test automatic operation. Testing of automatic opera-
tion  can  be  accomplished  by  turning  off  the  Utility 
power  supply  to  the  transfer  switch. When  the  utility 
power  is  turned  off,  the  standby  generator  should 
crank  and  start.  Following  startup,  transfer  to  the 
standby source should occur. Refer to Section 1.8 in 
this manual.
Following generator startup and transfer to the standby 
source, turn ON the utility power supply to the transfer 
switch.  Retransfer  back  to  the  “Utility”  source  should 
occur. After an “engine cooldown timer” has timed out, 
generator shutdown should occur. 
RESULTS: 
1.  If  normal  automatic  operation  is  obtained,  discontinue 
tests.
2.  If engine does not crank when utility power is turned off, 
proceed to Problem 15 Flow Chart, Section 4.3.
3.  If  engine  cranks  but  won’t  start,  go  to  Problem  17  in 
Section 4.3. 
4.  If  engine  cranks  and  starts,  but  transfer  to “Standby” 
does NOT occur, go to Problem 7 in Section 3.3.
5.  If  transfer  to “Standby”  occurs,  but  retransfer  back  to 
“Utility”  does  NOT  occur  when  utility  source  voltage  is 
restored, go to Problem 8 in Section 3.3.
teSt 57 – try a manual Start 
DISCUSSION: 
The  first  step  in  troubleshooting  for  an “engine  won’t 
crank”  condition  is  to  determine  if  the  problem  is 
peculiar to automatic operations only or if the engine 
won’t crank manually either.
PROCEDURE:
1.  On  the  generator  panel,  set  the  AUTO-OFF-MANUAL 
switch to OFF.
2.  Set the generator main line circuit breaker to its OFF (or 
open) position.
3.  Set the generator AUTO-OFF-MANUAL switch to MANUAL.
a.  The  engine  should  crank  cyclically  through  it’s 
“crank-rest” cycles until it starts.
b.  Let the engine stabilize and warm up for a few 
minutes after it starts.
RESULTS:
1.  If  the  engine  cranks  manually  but  does  not  crank 
automatically, go to Problem 15, Section 4.3.
2.  If  the  engine  does  not  crank  manually,  proceed  to 
Problem 16 in the “Troubleshooting Flow Charts”.
teSt 58 – auto-oFF-manual SWitch 
(V-tWin only)
PROCEDURE:
1.  Press  the “ESC”  key  on  the  controller  until  the  home 
page is reached.
2.  Press  the  right  arrow  key  until “Debug”  flashes.  Press 
“Enter” and the following screen will appear. See Figure 
2, Screen 2.
3.  Press “Enter” when “Inputs” is flashing.
4.  With  the  Inputs  Screen  displayed,  place  the  AUTO-
OFF-MANUAL  switch  to  the  AUTO  Position.  If  the 
controller  reads  an  input  from  the  switch,  Input  7  will 
change from “0” to “1”.
DC CONTROL
Part 4