York P2LBX16F14501 사용자 설명서

다운로드
페이지 36
 
13 
TABLE A-4: DIRECT DRIVE BLOWER CHARACTERISTICS 
CFM 
External Static Pressure – inches w.c. 
FURNACE 
MODEL
 
BLOWER 
MOTOR 
HP
 
MOTOR 
FLA
 
TEMP. 
RISE 
(
∆∆∆∆
T)
 
SPEED 
0.20  0.30 0.40 0.50 0.60 
High  1469 1386 1308 1213 1123 
Med-High 1377 1308 1224 1143 1063 
Med-Low 1088  1075 1038  985  916 
P3DHX12F08001 
GT10 
½ 
7.7 
70° - 90°F 
Low  721 721 712 688 649 
High  1752 1691 1659 1593 1525 
Med-High 1454 1454 1417 1379 1300 
Med-Low 975 944 912 879 844 
P2DHX16F12001 
G12-10 
1/2 
7.7 
70° - 90°F 
Low  631 593 552 515 486 
High  1810 1740 1675 1585 1510 
Med-High 1570 1540 1495 1445 1375 
Med-Low 1090 1080 1070 1065 1050 
P2LBX16F14501 
G10 
1/2 
7.7 
70° - 90°F 
Low  710 700 690 665 650 
 
TABLE A-5: BELT DRIVE BLOWER CHARACTERISTICS 
CFM 
External Static Pressure – Inches water column 
Furnace Model 
Motor HP 
Motor 
FLA 
∆∆∆∆
Blower 
Blower 
Pulley 
Motor 
Pulley 
Turns 
Out 
0.20 0.30 0.40 0.50 0.60 
0  2274 2080 1847 1532 1099 
2  2107 1927 1712 1420 1019 
4  1939 1775 1576 1308  939 
P4LBX20F19001 
3/4 HP 
13.0 
85°F 
G12 
7 x ¾ 
6  1772 1622 1441 1196  859 
 
TIP: 
These formulae will assist with the design of the ductwork and the determination of airflow delivery: 
(
)
(
)
CFM
Bonnet Output
x SystemTemperature Rise
SystemTemperature Rise
Bonnet Output
x CFM
=
=
1085
1085
.
.