York P2LBX16F14501 사용자 설명서

다운로드
페이지 36
 
 
25 
 
Table C-2:  R7184 Troubleshooting 
continued from previous page
 
Procedure Status  Corrective 
Action 
Indicator light is on. 
Remount control onto burner housing. Go to step 6. 
10.  Check cad cell. 
• 
Disconnect line voltage 
power and open line switch. 
• 
Remove existing cad cell 
and replace with new cad 
cell. 
• 
Disconnect all wires from 
thermostat terminals to en-
sure that there is no call for 
heat. 
• 
Reconnect line voltage 
power and close line switch. 
• 
Expose new cad cell to 
bright light such as a flash-
light. 
Indicator light is off. 
Go to step 11. 
Indicator light is on. 
Replace cad cell bracket assembly. 
11.  Check cad cell bracket as-
sembly. 
• 
Disconnect line voltage 
power and open line switch. 
• 
Remove cad cell wires from 
quick connect connectors 
on the  and leave control 
leadwires open. 
• 
Apply power to device. 
• 
Place jumper across cad 
cell terminals after burner 
motor turns on. 
Indicator light is off. 
Replace R7184. 
NOTE: Restricted Mode - (Limited Reset): In order to limit the accumulation of unburned oil in the combustion chamber, the con-
trol can be reset only 3 times, after which, the control locks out. The reset count returns to zero each time a call for heat 
is successfully completed. 
To reset from R
ESTRICTED 
M
ODE
: press and hold the reset button for 30 seconds. When the LED flashes twice, the de-
vice has reset. 
NOTE: Disable function: Pressing and holding the reset button will disable all functions until the button is released. The burner 
will restart at the beginning of the normal heat cycle on 
SAFETY CHECK
 
 
TABLE C-3:  SYSTEM AND GENERAL TROUBLESHOOTING 
Problem Possible 
Cause 
Remedy 
Thermostat not calling for heat. 
Check thermostat and adjust. Also, check thermostat for accu-
racy; if it is a mercury switch type, it might be off level. 
No power to furnace. 
Check furnace switch, main electrical panel furnace fuse or cir-
cuit breaker. Also look for any other hand operated switch, such 
as an old poorly located furnace switch, which was not removed 
during furnace replacement. 
Thermostat faulty. 
Remove thermostat wires from oil primary control terminals T-T. 
Place a jumper across T-T. If furnace starts, replace thermostat, 
thermostat sub-base (if equipped), or both. 
Furnace will not start. 
Oil primary control faulty. 
Check reset button on oil primary control. Remove thermostat 
wires from oil primary control terminals T1 - T2. Check for 24v 
across T -T. If no voltage is present, check for 115v to oil pri-
mary control. If 115v is present, go to Table C-2. 
Continues on next page