TC12 Installation, Commissioning & Maintenance Handbook 
3.3.3.72  Override Digital Outputs Timeout (GOT) 
GOT=(1-254 minutes, 255 disable timecount) 
Comment:   Displays the current timeout value, normally one minute. With a 
special PLD (667/1/12399/106 - VMS + LMU), the value can be 
changed. Without the special PLD, the value will always return one 
minute for reasons of safety.  
Note  The timeout facility is only present on PB392 issue 6 or later firmware. 
{Issues 4 and 5 include GOT but the timeout is in seconds.} 
 
3.3.3.73  Digital Outputs Override Data (GOD) 
GOD (Control byte number: 0-2) = (binary byte: 0 - 11111111) 
Comment: 
Allows test data patterns for up to three control bytes to be entered. 
The data is actually output when the override is enabled using the 
GOO command. 
 
3.3.3.74  Transmit Confirm Override data (GTC) 
GTC = (0 - 1) 
Comment: 
In conjunction with the GOO command enables the state of the 
Transmit confirm LED output to be manually controlled. 
 
3.3.3.75  Default Digital Outputs (GDO, GDT) 
These commands define the default state of the outputs, i.e. the state to which 
the outputs default when the override is removed. Only available with special 
667/1/12399/106 PLD.  
 
3.3.3.76  OTU Reply Time (GTR) 
GTR<enter> 
Comment: 
Displays the time in milliseconds after receipt of the sync byte that 
the OTU will start its reply message. 
 
 
High Occupancy Commands 
Note that the HIOCC software is based upon a TRRL algorithm. For further details 
regarding operation and use of this algorithm see "TRRL Supplementary report 
526, Automatic Incident Detection TRRL Algorithms HIOCC and PATREG". 
 
3.3.3.77 High 
Occupancy 
Alarm threshold (GHA) 
GHA {unit number: 0-7} = {percentage occupancy: 0-100} (100
Comment: 
Occupancy alarm threshold (0 - 100%), is used to determine alarm 
conditions.  
 
666/HE/43100/000  
Page 114 
Issue 9