TC12 Installation, Commissioning & Maintenance Handbook 
2.2.4
 before the mains cable is plugged into the PCB. Similarly 
hen the PSU PCB is being removed, disconnect the mains plug from the mains 
socket on the PCB, bef
r earth straps are situated 
on the right-hand 19" upright of the Inst
available at the correct height for up to four racks of TC12 that may be installed. 
The earth strap comes with a bolt (+ star washer) and tag on one end which is 
attached to the hole situated below the power supply on the PCB (see Figure 7 for 
position of ground hole). 
 
The switches on the PSU PCB should be set as follows: 
 
(See Figure 8 for diagrams of switch settings) 
 
S1 - PC Address 
This should be set to '1'. If a second rack is fitted in the Instation then the position 
of the switch, on the PSU Board in the second rack, does not matter. If there is 
more than one PC connected to the same Ethernet link, the switch should be set 
to 2 for the PSU Board connected to the second PC, 3 for the PSU Board 
associated with the third PC, etc. The switch setting should correspond to the last 
digit of the TC12 PC SCN in the associated UTC System’s database. 
 
 
S2 - Audio Alarm Configuration Switch 
This is a 4-way DIL switch. The usual setting for this switch is as follows: 
switch position 1 should be closed 
switches 2, 3 and 4 should be open. 
 
The function of this switch is to enable certain inputs to the board, to cause the low 
frequency alarm tone to sound.  
 
Switch position 
Input signal 

Audio 2 Signal 
The high frequency alarm tone is sounded if the Audio 2 Signal becomes active. 
This is not configurable. It can only be disabled using the audio on/off switch (see 
below). 
.1  PSU PCB (inc. Digi I/O, SIP (local and remote), Watchdog and TC8 cables) 
See Figure 7 for a diagram of the board layout showing the position of connectors
LEDs, switches, volume control. 
 
SAFETY NOTE  
When installing the PSU PCB in the TC12 Instation cabinet the earth strap should 
be bolted on to the PCB
w
ore removing the earth strap. Fou
ation cabinet, i.e. there is one strap 
Audio 1 Signal 
Failure of PC 
Failure of UTC TCC 
 
Closing the appropriate switch causes the input signal indicated to cause a low 
frequency alarm tone, should the signal become active. Note if more than one 
switch is closed, any of the associated input signals becoming active, will cause 
e alarm to sound. 
th
 
666/HE/43100/000  
Page 23 
Issue 9