Combustion
Air Supply
Exhaust
Configuration
Heater Venting
Category
Certified
Materials
Combustion Air
Inlet Material
Vertical Natural 
Draft Venting
I
“B” Vent
From Inside Building
(Non-Direct Venting)
Horizontal Through-
the-Wall Venting
III
Stainless Steel
(Gas Tight)
Vertical Natural 
Draft Venting
I
“B” Vent
From Outside Building
(Direct Venting)
Horizontal Through-
the-Wall Venting
III
Stainless Steel
(Gas Tight)
Galvanized Steel
PVC
ABS
CPVC
Support of Vent Stack
The weight of the vent stack or chimney must not rest
on the heater vent connection. Support must be pro-
vided  in  compliance  with  applicable  codes.  The  vent
should also be installed to maintain proper clearances
from combustible materials.
Use insulated vent pipe spacers where the vent pass-
es through combustible roofs and walls.
Vent Terminal Location
1. Condensate  can  freeze  on  the  vent  cap.  Frozen
condensate on the vent cap can result in a blocked
flue condition.
2. Give  special  attention  to  the  location  of  the  vent
termination  to  avoid  possibility  of  property  dam-
age or personal injury.
3. Gases  may  form  a  white  vapor  plume  in  winter.
The plume could obstruct a window view if the ter-
mination is installed near windows.
4. Prevailing winds, in combination with below-freez-
ing  temperatures,  can  cause  freezing  of
condensate  and  water/ice  build-up  on  buildings,
plants or roofs.
5. The bottom of the vent terminal and the air intake
shall be located at least 12 in. above grade, includ-
ing normal snow line.
6. Un-insulated single-wall metal vent pipe shall not
be used outdoors in cold climates for venting gas-
fired equipment.
7. Through-the-wall  vents  for  Category  II  and  IV
appliances and non-categorized condensing appli-
ances shall not terminate over public walkways or
over  an  area  where  condensate  or  vapor  could
create a nuisance or hazard or could be detrimen-
tal to the operation of regulators, relief valves, or
other  equipment.  Where  local  experience  indi-
cates that condensate is a problem with Category
I and III appliances, this provision shall also apply.
CAUTION: When  condensate  traps  are  installed,
condensate  must  be  routed  to  an  appropriate
container  for  neutralization  before  disposal,  as
required by local codes. 
WARNING: Contact  the  manufacturer  of  the  vent
material if there is any question about the appliance
categorization  and  suitability  of  a  vent  material  for
application  on  a  Category  III  or  IV  vent  system.
Using  improper  venting  materials  can  result  in
personal injury, death or property damage. 
NOTE: During  winter  months  check  the  vent  cap
and make sure no blockage occurs from build-up of
snow or ice.
Table M:  Venting Category Requirements