Siemens ST PCS 7 사용자 설명서

다운로드
페이지 344
Process I/O
ET 200iSP distributed I/O
Electronics modules and watchdog module
11/35
Siemens ST PCS 7 · November 2007
11
Selection and Ordering Data
Order No.
Digital electronics modules
 
Digital input modules
8 DI NAMUR
For evaluation of NAMUR sen-
sors, connected/non-connected 
contacts, as well as for recording 
counter pulses or measuring fre-
quencies
• 8 x NAMUR (NAMUR sensor 
on/off, NAMUR changeover 
contact) or connected/
non-connected inputs 
(single/changeover contact)
• 2 channels optionally usable as 
counters (max. 5 kHz) or fre-
quency meters (1 Hz ... 5 kHz)
• Time tagging 5 ms, rising or fall-
ing edge
• Wire break monitoring
• Short-circuit monitoring
• Sensor power supply monitoring
• Flutter monitoring
6ES7 131-7RF00-0AB0
B)
Digital output module with
H switch-off 
(external actuator switch-off via 
H-signal); 
for switching of solenoid valves, 
DC relays, signal lamps, actua-
tors
4 DO DC 23.1 V/20 mA
• 4 channels with 20 mA each
• Short-circuit monitoring
• Wire break monitoring
• Parameterizable connection of 
substitute value in case of CPU 
failure
• Load-free switching of outputs 
via external intrinsically-safe 
signal
6ES7 132-7RD01-0AB0
B)
4 DO DC 17.4 V/27 mA
• 4 channels with 27 mA each or
• 2 outputs connected in parallel 
with 54 mA each 
• Short-circuit monitoring
• Wire break monitoring
• Parameterizable connection of 
substitute value in case of CPU 
failure
• Load-free switching of outputs 
via external intrinsically-safe sig-
nal
6ES7 132-7RD11-0AB0
4 DO DC 17.4 V/40 mA
• 4 channels with 40 mA each or
• 2 outputs connected in parallel 
with 80 mA each 
• Short-circuit monitoring
• Wire break monitoring
• Parameterizable connection of 
substitute value in case of CPU 
failure
• Load-free switching of outputs 
via external intrinsically-safe sig-
nal
6ES7 132-7RD21-0AB0
Digital output module with
L switch-off 
(external actuator switch-off via 
L-signal); 
for switching of solenoid valves, 
DC relays, signal lamps, actua-
tors
4 DO DC 23.1 V/20 mA
• 4 channels with 20 mA each
• Short-circuit monitoring
• Wire break monitoring
• Parameterizable connection of 
substitute value in case of CPU 
failure
• Load-free switching of outputs 
via external intrinsically-safe 
signal
6ES7 132-7GD00-0AB0
B)
4 DO DC 17.4 V/27 mA
• 4 channels with 27 mA each or
• 2 outputs connected in parallel 
with 54 mA each 
• Short-circuit monitoring
• Wire break monitoring
• Parameterizable connection of 
substitute value in case of CPU 
failure
• Load-free switching of outputs 
via external intrinsically-safe sig-
nal
6ES7 132-7GD10-0AB0
4 DO DC 17.4 V/40 mA
• 4 channels with 40 mA each or
• 2 outputs connected in parallel 
with 80 mA each 
• Short-circuit monitoring
• Wire break monitoring
• Parameterizable connection of 
substitute value in case of CPU 
failure
• Load-free switching of outputs 
via external intrinsically-safe sig-
nal
6ES7 132-7GD20-0AB0
B) Subject to export regulations: AL: N, ECCN: EAR99H
Selection and Ordering Data
Order No.
© Siemens AG 2007