SJ300 Inverter
T
roub
leshooting
and Maintenance
6–3
Troubleshooting 
Tips
The table below lists typical symptoms and the corresponding solution(s). 
Symptom/condition
Probable Cause
Solution
The motor 
will not run.
The inverter 
outputs U, V, W 
are not supplying 
voltage.
• Is the frequency command source 
A001 parameter setting correct?
• Is the Run command source A002 
parameter setting correct?
• Make sure the parameter 
setting A001 is correct.
• Make sure the parameter 
setting A002 is correct.
• Is power being supplied to terminals
 [R], [S], and [T] ([L1], [L2], and 
[L3])? If so, the POWER lamp should 
be ON.
• Check terminals [R], [S], and 
[T] ([L1], [L2], and [L3]), then 
[U], [V], and [W] ([T1], [T2], 
and [T3]).
• Turn ON the power supply or 
check fuses.
• Is there an error code 
EXX.X
 
displayed?
• Press the Func. key and deter-
mine the error type. Eliminate 
the error cause, then clear the 
error (Reset).
• Are the signals to the intelligent input 
terminals correct?
• Is the Run Command active?
• Is the [FW] terminal (or [RV]) 
connected to P24 (via switch, etc.)
• Verify the terminal functions 
for C001 - C008 are correct.
• Turn ON Run command 
enable.
• Supply 24V to [FW] or [RV] 
terminal, if configured.
• Has the frequency setting for F001 
been set greater than zero?
• Are the control circuit terminals [H], 
[O], and [L] connected to the potenti-
ometer?
• Set the parameter for F001 to a 
safe, non-zero value.
• If the potentiometer is the 
frequency setting source, verify 
voltage at [O] > 0V.
• Is the RS (reset) function or FRS (free-
run stop) function ON?
• Turn OFF the command(s).
Inverter outputs 
U, V, W are 
supplying voltage.
• Is the motor load too heavy?
• Reduce load or test the motor 
independently of the load.
The direction of the motor is 
reversed.
• Are the connections of output termi-
nals [U/T1], [V/T2], and [W/T3] 
correct?
• Is the phase sequence of the motor 
forward or reverse with respect to
[U/T1],[V/T2], and [W/T3]?
• Make connections according to 
the phase sequence of the 
motor. In general:
FWD = U-V-W, and REV=U-
W-V.
• Are the control terminals [FW] and 
[RV] wired correctly?
• Is parameter F004 properly set?
• Use terminal [FW] for forward, 
and [RV] for reverse.
• Set motor direction in F004.