Monitoring Trip Events, History, & Conditions
T
roub
leshooting
and Maintenance
6–6
E05
Overload protection
When a motor overload is detected by the 
electronic thermal function, the inverter trips and 
turns OFF its output.
E06
Braking resistor overload
When the regenerative braking resistor exceeds 
the usage time allowance or usage ratio, the 
inverter trips and turns OFF its output to the 
motor.
E07
Over voltage protection
When the DC bus voltage exceeds a threshold, due 
to regenerative energy from the motor.
E08
EEPROM error
When the built-in EEPROM memory has 
problems due to noise or excessive temperature, 
the inverter trips and turns OFF its output to the 
motor.
E09
Under-voltage error
A decrease of internal DC bus voltage below a 
threshold results in a control circuit fault. This 
condition can also generate excessive motor heat 
or cause low torque. The inverter trips and turns 
OFF its output.
E10
CT (current transformer) 
error
If a strong source of electrical interference is close 
to the inverter or a fault occurs in a built-in CT 
(current transformer), the inverter trips and turns 
its output OFF.
E11
CPU error
A malfunction in the built-in CPU has occurred, 
so the inverter trips and turns OFF its output to the 
motor.
E12
External trip
A signal on an intelligent input terminal config-
ured as EXT has occurred. The inverter trips and 
turns OFF the output to the motor.
E13
USP
When the Unattended Start Protection (USP) is 
enabled, an error occurred when power is applied 
while a Run signal is present. The inverter trips 
and does not go into Run Mode until the error is 
cleared.
E14
Ground fault
The inverter is protected by the detection of 
ground faults between the inverter output and the 
motor during powerup tests. This feature protects 
the inverter, and does not protect humans. 
E15
Input over-voltage
When the input voltage is higher than the specified 
value, it is detected 60 seconds after powerup and 
the inverter trips and turns OFF its output.
E16
Instantaneous power failure
When the input power is removed for more than 
15ms, the inverter trips and the output to the motor 
turns OFF. If the power failure duration exceeds 
the duration set in parameter B002, it is consid-
ered a power failure. When input power is 
restored, the inverter restarts if the Run signal is 
present, depending on the restart condition.
E21
Inverter thermal trip
When the inverter internal temperature is above 
the threshold, the thermal sensor in the inverter 
module detects the excessive temperature of the 
power devices and trips, turning the inverter 
output OFF.
Error 
Code
Name
Probable Cause(s)