Hitachi SJ300-037HFE 사용자 설명서

다운로드
페이지 289
Communications Reference Information
Append
ix
 B
B–18
Block Check 
Code (BCC)
This section shows how the inverter protocol computes defines a BCC—block check code. The 
BCC is calculated for each frame transmitted and can be used to verify the integrity of data 
transmission. The example below shows command 01 setting the inverter frequency to 5Hz.
The block check code is computed by using the ASCII codes (shown above) and applying 
eXclusive OR (XOR) operations. Beginning with the first pair of bytes, the result of their XOR 
result is then used in an XOR operation with the third byte, and so on. For this example, the 
BCC calculation is shown below.
ASCII Code Table
The table below shows only the ASCII codes used for function codes and parameter data.
STX Node
Command
Data
BCC [CR]
Frame format
ASCII Code
(0x 02)
(0x 30 31)
(0x 30 31)
(0x 30 30 30 35 30 30)
(0x 30 35)
(0x 0D)
0 1
0 1
0 0 0 5 0 0
0
Data bytes:
3 0
3 0
3 5
3 0
3 0
3 0
3 1
3 0
3 1
0 1
3 0
3 1
0 0
3 0
0 0
3 0
0 5
3 5
0 5
BCC
XOR
intermediate results
Character
ASCII Code
Character
ASCII Code
Character
ASCII Code
STX
0 2
4
3 4
C
4 3
ACK
0 6
5
3 5
D
4 4
CR
0 D
6
3 6
E
4 5
NAK
1 5
7
3 7
F
4 6
0
3  0
8
38
H
4  8
1
3  1
9
39
P
5  0
2
3 2
A
4 1
3
3 3
B
4 2