Hitachi SJ300-037HFE 사용자 설명서

다운로드
페이지 289
SJ300 Inverter
Appe
ndi
x D
D–3
6. Follow safety measures in the filter installation.
• Ensure that the protective earth terminal (PE) of the filter is properly connected to the PE 
terminal of the adjustable frequency inverter. An HF ground connection via metal 
contact between the housings of the filter and the adjustable frequency inverter, or solely 
via cable shield, is not permitted as a protective conductor connection. The filter must be 
solidly and permanently connected with the ground potential
 so as to preclude the danger 
of electric shock upon touching the filter if a fault occurs.
To achieve a protective ground connection for the filter:
• Ground the filter with a conductor of at least 10 mm
2
 cross-sectional area.
• Connect a second grounding conductor, using a separate grounding terminal parallel to 
the protective conductor. (The cross section of each single protective conductor terminal 
must be sized for the required nominal load.)
PE
L1
L2
L3
SJ300 inverter with footprint-type filter
SJ300 inverter with book-type filter
PE
L1
L2
L3
M
3~
M
3~