The inverter has the capability to accept external analog inputs that can command the output 
frequency to the motor. Signals including voltage input (0 to +10V) at terminal [O], bipolar 
input (-10 to +10V) at terminal [O2], and current input (4 to 20mA) at terminal [OI] are avail-
able. Terminal [L] serves as signal ground for the three analog inputs. The analog input settings 
adjust the curve characteristics between the analog input and the frequency output.
Adjusting [O–L] characteristics – In the 
graph to the right, A013 and A014 select 
the active portion of the input voltage 
range. Parameters A011 and A012 select 
the start and end frequency of the 
converted output frequency range, respec-
tively. Together, these four parameters 
define the major line segment as shown. 
When the line does not begin at the origin 
(A011 and A013 > 0), then A015 defines 
whether the inverter outputs 0Hz or the 
A011-specified frequency when the 
analog input value is less than the A013 
setting. When the input voltage is greater 
than the A014 ending value, the inverter 
outputs the ending frequency specified by 
A012.
Adjusting [OI–L] characteristics – In 
the graph to the right, A103 and A104 
select the active portion of the input 
current range. Parameters A101 and A102 
select the start and end frequency of the 
converted output frequency range, respec-
tively. Together, these four parameters 
define the major line segment as shown. 
When the line does not begin at the origin 
(A101 and A103 > 0), then A105 defines 
whether the inverter outputs 0Hz or the 
A101-specified frequency when the 
analog input value is less than the A103 
setting. When the input voltage is greater 
than the A104 ending value, the inverter 
outputs the ending frequency specified by 
A102.
Adjusting [O2–L] characteristics – In 
the graph to the right, A113 and A114 
select the active portion of the input 
voltage range. Parameters A111 and 
A112 select the start and end frequency of 
the converted output frequency range, 
respectively. Together, these four parame-
ters define the major line segment as 
shown. When the input voltage is less 
than the A113 input starting value, the 
inverter outputs the starting frequency 
specified by A111. When the input 
voltage is greater than the A114 ending 
value, the inverter outputs the ending 
frequency specified by A112.
%  input 
100%
10V
0%
0V
f
max. frequency
A013
A014
A012
A011
A015=0
A015=1
%  input 
100%
20mA
0%
4mA
A102
f
max. frequency
A101
A103
A104
A105=0
A105=1
%  input 
+100%
+10V
0
A112
f
max. fwd frequency
A111
A113
A114
–100%
-10V
f
max. rev frequency