20 
Example Wiring Diagram
 
The schematic diagram below provides a general example of logic connector wiring, in 
addition to basic power and motor wiring converted in Chapter 2. The goal of this chapter 
is to help you determine the proper connections for the various terminals shown below for 
your application needs. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Breaker, MCCB 
or GFI 
Power source, 
3-phase or 
1-phase, per 
inverter model 
AM
Meter 
H
L
Analog reference 
0~10VDC 
4~20mA 
GND for analog signals 
WJ200 
 
Motor
PD/+1 
P/+
R
(L1)
S
(L2)
T
N(L3)
U
(T1)
V
(T2)
W
(T3)
N/-
DC reactor 
(optional) 
AL1 
AL0 
AL2 
Relay contacts, 
type 1 Form C 
EO
Meter 
Pulse train input 
24Vdc 32kHz max. 
RB
 
Brake 
resistor 
(optional) 
11/EDM 
Load 
Freq. arrival signal 
Open collector output 
Output circuit 
GND for logic outputs 
12
Load 
-
CM2
L
+
-
O
OI
EA
Apprx.10k
Ω 
10Vdc 
Apprx.100
Ω 
RS485 
transceiver
RJ45 port 
(Optional operator port) 
USB 
transceiver
USB (mini-B) port 
(PC communication port) 
USB power: Self power 
L
L
Option port 
controller
Option port connector 
L
L
SP
SN
RS485 
transceiver
Termination resistor (200
Ω)
(Change by slide switch) 
Serial communication port 
(RS485/Modbus) 
Forward
Thermistor 
Intelligent inputs, 
7 terminals 
GND for logic inputs 
NOTE: For the wiring 
of intelligent I/O and 
analog inputs, be sure 
to use twisted pair / 
shielded cable. Attach 
the shielded wire for 
each signal to its 
respective common 
terminal at the inverter 
end only. 
Input impedance of 
each intelligent input is 
4.7k
Ω 
Jumper wire
(Sink logic) 
NOTE: Common for 
RS485 is “L”. 
Braking 
unit (optional) 
24V 
P24 
+ - 
1
2
3/GS1 
4/GS2 
5/PTC 
6
7/EB 
PLC 
L
Input 
circuits 
[5] configurable as 
discrete input or 
thermistor input