28 
The two diagrams below input wiring circuits using the inverter’s internal +24V supply. 
Each diagram shows the connection for simple switches, or for a field device with 
transistor outputs. Note that in the lower diagram, it is necessary to connect terminal [L] 
only when using the field device with transistors. Be sure to use the correct connection of 
the jumper wire shown for each wiring diagram. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Sinking Inputs, Internal Supply
Jumper wire
 = [PLC] – [P24] position 
GND
Field device 
Open collector outputs, 
NPN transistors 
WJ200 
P24 
1
7
24V 
PLC 
Input 
circuits
-
Logic GND 
Input common
Jumper wire
Input switches
L
Sourcing Inputs, Internal Supply 
Jumper wire
 = [PLC] – [L] position
Common to 
[P24] 
Field device 
PNP transistor 
sousing outputs 
WJ200 
P24 
1
7
24V 
PLC 
Input 
circuits
-
Logic GND 
Input common
Jumper wire
Input switches
L
GND
to PNP bias 
circuits