Hitachi SJ700-2 Series 사용자 설명서

다운로드
페이지 81
1 - 2 
1.2 Precautions for Data Setting 
The default display mode limits the screens (parameters) that can be displayed on the monitor. To enable the display 
of all parameters, specify "00" (full display) for the function code display restriction (b037). 
To enable the parameters to be changed while the inverter is operating, specify "10" for the software lock mode 
selection (b031). 
 
1.2.1 Monitoring Mode 
 
Code 
Function name 
Monitored data or setting 
Default 
Note 
d001 
Output frequency monitoring 
0.00 to 99.99, 100.0 to 400.0 (Hz) 
 
 
d002 
Output current monitoring 
0.0 to 999.9, 1000 to 9999 (A) 
 
 
d003 
Rotation direction minitoring 
F (forward rotation), o (stopped), r (reverse rotation) 
 
 
d004 
Process variable (PV), PID feedback 
monitoring 
0.00 to 99.99, 100.0 to 999.9, 1000. to 9999. 
1000 to 9999 (10000 to 99990),  100 to  999 (100000 to 999000) 
 
 
d005 
Intelligent input terminal status 
(Example) 
Terminals FW, 7, 2, and 1: ON 
Terminals 8, 6, 5, 4, and 3: OFF 
 
 
 
 
 
 
 
d006 
Intelligent output terminal status 
(Example) 
Terminals 12 and 11: ON 
Terminals AL, 15, 14, and 13: OFF 
 
 
 
 
 
 
d007 
Scaled output frequency monitoring 
0.00 to 99.99, 100.0 to 999.9, 1000. to 9999., 1000 to 3996 (10000 to 39960) 
 
 
d008 
Actual-frequency monitoring 
-400. to -100., -99.9 to 0.00 to 99.99, 100.0 to 400.0 (Hz) 
 
 
d009 
Torque command monitoring 
-200. to +200. (%) 
 
 
d010 
Torque bias monitoring 
-200. to +200. (%) 
 
 
d012 
Torque monitoring 
-200. to +200. (%) 
 
 
d013 
Output voltage monitoring 
0.0 to 600.0 (V) 
 
 
d014 
Power monitoring 
0.0 to 999.9 (kW) 
 
 
d015 
Cumulative power monitoring 
0.0 to 999.9, 1000. to 9999. 
1000 to 9999 (10000 to 99990),  100 to  999 (100000 to 999000) 
 
 
d016 
Cumulative operation RUN time 
monitoring 
0. to 9999., 1000 to 9999 (10000 to 99990),  100 to  999 (100000 to 999000) (hr) 
 
 
d017 
Cumulative power-on time monitoring 
0. to 9999., 1000 to 9999 (10000 to 99990),  100 to  999 (100000 to 999000) (hr) 
 
 
d018 
Heat sink temperature monitoring 
-020. to 200.0 ( C) 
 
 
d019 
Motor temperature monitoring 
-020. to 200.0 ( C) 
 
 
d022 
Life-check monitoring 
1:  Capacitor on main circuit board 
2:  Cooling-fan speed drop 
 
 
 
 
 
 
 
 
d023 
Program counter 
0 to 1024 
 
 
d024 
Program number monitoring 
0000 to 9999 
 
 
FW 
3  2 
AL  15 14  13 12 
11 
ON 
OFF