Nortel Networks 411-2021-111 사용자 설명서
DualMode Metrocell Cell Site Specifications
7-5
DMS-MTX DualMode Metrocell Cell Site Description
Earthquake
Meet earthquake requirements of Zone 1
and Zone 2 as defined by Bellcore
TR-NWT-000063
and Zone 2 as defined by Bellcore
TR-NWT-000063
Fixed equipment anchorage.
Thermal dissipation for Metrocell RF Frame:
Regulatory
Electromagnetic Emissions
Cell site equipment complies with the following Regulatory Specification:
•
FCC part 22 for 800 MHz frequency
•
FCC part 15 Class B for cell site with Universal CE Frame and Metro RF
Frame (except for the ICRM, CSM, HSMO and ACU shelves located on
the Universal CE Frame)
the Universal CE Frame)
•
DOC RSS-128 Issue 1.0 Dual Mode Capability in Canada
|
Radiated Emissions
Cell site equipment complies with the following Regulatory Specification:
•
FCC Part 22 for 800 MHz frequency
•
FCC Part 15 Class B for cell site with Universal CE Frame and Metro RF
Frame (except for the ICRM, CSM, HSMO and ACU shelves located on
the Universal CE Frame)
the Universal CE Frame)
•
Bell Canada Design Standard TAD 8465 of Bellcore TR-NWT-001089 in
10 kHz to 30 MHz and 1 GHz to 10 GHz range for radiated emission
Telecom Compliance
Cell site equipment complies with the following Regulatory Specification:
•
CS03, Issue 7, Part 2 (Table 1: Digital Interface Requirement, Type IV)
•
FCC Part 68 (TSB31, Table 4.5-2: Test Requirement Matrix)
Component
Dissipation per
unit
Maximum
number of units
Total
dissipation
TRU
27 W
24
648 W
PA
89 W
24
2136 W
Combiner (-4.5 dB)
21 W
24
504 W
Duplexer (-0.7 dB)
9.3 W
3
28 W
Total
3.3 KW