Electrical Connections 
The MR1 Mini-Remote requires a two-wire connection (field-
supplied) to communicate with the Environmental unit under its 
control. The stranded twisted-pair connects to the MR1 interface 
board at TB2-11 (T+) and TB2-12 (T-).  Refer to Table 1 below 
for the connections at the Environmental unit.  Note that 
maximum length for RS-422 communications is 1000 feet, and 
minimum of 22 gauge wire should be used for all field wiring.
 
Power for the MR1 is supplied to TB3-1 and TB3-2. Maximum 
current draw is 0.3A at 24VAC.  It is recommended that the 
MR1 be powered independently from an external 24VAC 
transformer; optionally, it may draw power from the 
Environmental unit.  However, if the MR1 is located greater 
than 300 feet (100 meters) from the Environmental unit, an 
external transformer must be used.  
Caution: Ensure Environmental 
unit has sufficient 24VAC power 
to support the MR1, Liqui-tects 
or any other auxiliary device. 
Liebert 
Environmental 
Controller 
24VAC 
Auxiliary 
Power 
Connection to MR1 
TB2-11 (T+) 
TB2-12 (T-) 
SM - Standard  
AM/AG - Advanced  
L10 - Level 10  
Microprocessors 
Terminal T5 
Terminal G5 
Terminal 78 (T+) 
Terminal 77 (T-) 
L00 - Level 00 
Microprocessor 
TB1-1 
TB1-5 
Terminal 78 (T+) 
Terminal 77 (T-) 
Mini-Mate 2 
TB4-1 (T+) 
TB4-2 (T-) 
SSC - Small System 
Controller 
TB2-1 (T+) 
TB2-2 (T-) 
Table 1: Connection Summary 
The MR1 provides a Common Alarm Output, at TB2-9 and 
TB2-10.  This dry-contact is rated for 5A, at 24VDC or 
120VAC.  
There are four optional Customer Alarm inputs that may be used 
on the MR1 (see Hardware Configuration).  The inputs are 
triggered by contact-closures, and the contacts are rated for 5A, 
at 24VDC or 120VAC as well.  The connection points and 
display mapping are as follows: 
NOTE: New Feature. The inputs 
are now contact-closure – 
24VAC powered inputs are no 
longer necessary. 
Local Alarm 1:  
TB2-3   &  TB2-4 
NOTE: Exercise caution if 
installing new MR1 as 
replacement unit: remove power 
from signal inputs, or damage to 
unit may occur! 
Local Alarm 2: 
TB2-1   &  TB2-2 
High Water Alarm:  TB2-5   &  TB2-6 
High Head Alarm:  TB2-7   &  TB2-8 
 
Liebert MR1  5 