AOP Start-Up & Initialization 
 
Siemens Building Technologies, Inc. 
 
4. 
Use 
 and 
 to scroll through the parameters and to highlight Command Source P0700
Press 
 to confirm the selection and the cursor advances to the parameter index.  
 
Use 
 and 
 to scroll through the indexes for P0700 and to highlight P0700[1] (index 1). 
Press 
 to confirm the selection and the cursor advances to the parameter value. 
 
Use 
 and 
 to set P0700[1]=4 (USS on BOP/AOP local link).  
Press 
 to confirm the setting and the cursor returns to the parameter.  
5. 
Use 
 and 
 to scroll through the parameters and to highlight Selection of Frequency 
Setpoint P1000. Press 
 to confirm the selection and the cursor advances to the parameter 
index.  
 
Use 
 and 
 to scroll through the indexes for P1000 and to highlight P1000[1] (index 1). 
Press 
 to confirm the selection and the cursor advances to the parameter value. 
 
Use 
 and 
 to set P1000[1]=1 (motor potentiometer [MOP] setpoint).  
Press 
 to confirm the setting and the cursor returns to the parameter. 
6. 
Use 
 and 
 to scroll through the parameters and to highlight Commissioning parameter 
P0010. Press 
 to confirm the selection and the cursor advances to the parameter value.  
 
Use 
 and 
 to set P0010[0]=0 (Ready) to exit the quick commissioning mode. Press 
 
to confirm the setting and the cursor returns to the parameter. 
7. 
Use 
 and 
 to scroll through the parameters and to highlight USS Telegram Off Time 
P2014. Press 
 to confirm the selection and the cursor advances to the parameter index.  
 
Use 
 and 
 to scroll through the indexes for P2014 and to highlight P2014[1] (index 1, 
Serial Interface BOP Link). Press 
 to confirm the selection and the cursor advances to the 
parameter value. 
 
Use 
 and 
 to set P2014[1]=5000 (USS on BOP/AOP local link) to prevent unexpected 
drive operation. In this mode, removal of the AOP from the SED2 VFD causes a timeout to 
occur in 5 seconds. Press 
 to confirm the setting and the cursor returns to the parameter. 
8. 
Press 
 to return to r0000. Press 
 to display the standard (operate) screen.  
9. 
Press 
 to switch the SED2 to hand mode.  
10. 
Press 
 to start the SED2.  
11. 
Use 
 to increase the output; Use 
 to decrease the output.