W7 ASD Installation and Operation Manual
19
II — The function of the II input is to receive a 4 – 20 mA input signal that controls a 0 – 80 Hz output. 
This input terminal may be programmed to control the speed or torque of the motor and may not be used 
when using the VI input. Also, the gain and bias of this terminal may be adjusted.
 
See 
 for more information on this terminal.
VI — The function of the VI input terminal is to receive a 0 – 10 VDC input signal that controls a 
 
0 – 80 Hz output. This input terminal may be programmed to control the speed or torque of the motor 
and may not be used when using the II input. Also, the gain and bias of this terminal may be adjusted.
 
See 
 for more information on this terminal.
P24 — +24 VDC @ 50 mA power supply for customer use.
PP — The function of output PP is to provide a 10 VDC output that may be divided using a 
potentiometer. The tapped voltage is applied to the RR input to provide manual control of the RR 
programmed function.
OUT1 — The default setting for this output terminal is Damper Command. This output terminal may 
be programmed to provide an indication that 1 of 60 possible events has taken place. This function may 
be used to signal external equipment or to activate the brake. The OUT1 contact is rated at 2A/250 
VAC. See 
 for more information on this terminal.
OUT2 — The default setting for this output terminal is ACC/DEC Complete. This output terminal 
may be programmed to provide an indication that 1 of 60 possible events has taken place. This function 
may be used to signal external equipment or to activate the brake. The OUT2 contact is rated at 2A/250 
VAC. See 
 for more information on this terminal.
FP — The default function of this output terminal is to output a series of pulses at a rate that is a 
function of the output frequency of the ASD. As the output frequency of the ASD goes up so does the 
FP output pulse rate. This terminal may be programmed to provide output pulses at a rate that is a 
function of the output frequency or the magnitude of any 1 of the 31 the functions listed in 
. See 
 for more information on this terminal.
AM — This output terminal produces an output current that is proportional to the output frequency of 
the ASD or of the magnitude of the function assigned to this terminal. The available assignments for 
this output terminal are listed in 
. Se
 for more 
information on this terminal.
FM — This output terminal produces an output current that is proportional to the output frequency of 
the ASD or of the magnitude of the function assigned to this terminal. The available assignments for 
this output terminal are listed in 
. See 
 for more 
information on this terminal.
FLC — FLC is the middle leg of a single-pole double-throw (relay) switch. This FLC contact of the 
relay is switched between FLB and FLA. This contact may be programmed to switch between FLB and 
FLA as a function of any 1 of the 60 conditions listed in 
FLB — One of two contacts that, under user-defined conditions, connect to FLC (see 
).
FLA — One of two contacts that, under user-defined conditions, connect to FLC (see 
).
Note:
The FLA and FLC contacts are rated at 2A/250 VAC. The FLB contact is rated at 
1A/250 VAC.
CC — Control common (Do Not connect to Earth Gnd).
Figure 4. FLA, FLB, and FLC switching contacts shown in the de-energized state.
Note:
The relay is shown in the Faulted or 
de-energized condition. During 
normal system operation the relay 
connection is FLC-to-FLA.