Magnetek TM7310rev01 사용자 설명서
Quattro DC Line Side Power Convert A5 Submenu
Line Side Power Converter A5 submenu
NOTE: The only parameter that should ever need to be adjusted is INPUT L-L VOLTS. Other
parameters are for Magnetek Engineering use only.
parameters are for Magnetek Engineering use only.
Run
lock
lock
out
Parameter Description Units
Default
Range
Hidden
Item
Id REG PROP GAIN
Proportional gain for out-of-
phase current regulator
phase current regulator
none
0.30
0.00 – 9.99
N N
Id REG INTEGRAL GAIN
Integral gain for out-of-
phase current regulator
phase current regulator
none
10
0 – 999
N N
Iq REG PROP GAIN
Proportional gain for in-
phase current regulator
phase current regulator
none
0.30
0.00 – 9.99
N N
Iq REG INTEGRAL GAIN
Integral gain for in-phase
current regulator
current regulator
none
40
0 – 999
N N
DC BUS REG P GAIN
Proportional gain for bus
voltage regulator
voltage regulator
none
3.00
0 – 9.99
N N
DC BUS REG I GAIN
Integral gain for bus voltage
regulator
regulator
none
40
0 – 999
N N
INPUT L-L VOLTS
(Input Line to Line Voltage -
Input Voltage)
This parameter sets the
input voltage or AC line
input voltage to the drive.
Input Voltage)
This parameter sets the
input voltage or AC line
input voltage to the drive.
volts
480
110 – 552
N Y
DC BUS V BOOST
(DC bus voltage reference)
Adjusts the DC bus voltage
boost above the peak of
line voltage.
Adjusts the DC bus voltage
boost above the peak of
line voltage.
Vdc
30
15 – 75
N N
SW BUS OV LEVEL
(Software Bus Overvoltage
Level) DC bus software
Overvoltage trip point.
Level) DC bus software
Overvoltage trip point.
Vdc
850
100 – 850
N N
BUS VREF SOURCE
(Bus Voltage Reference
Source) Selects the bus
voltage boost reference.
• Track Line V uses the
Source) Selects the bus
voltage boost reference.
• Track Line V uses the
actual line voltage for the
bus reference.
Recommended for
systems with a stiff line.
bus reference.
Recommended for
systems with a stiff line.
• Trk Vin Param uses
INPUT L-L VOLTS (A5)
for the bus reference.
Recommended to
systems with a soft line.
for the bus reference.
Recommended to
systems with a soft line.
none
Trk Vin
Param
1= Track Line V
2= Trk
2= Trk
Vin
Param
N N
PLL FILTER FC
(Phase Locked Loop Filter
Frequency) Utility line
Phase Locked Loop filter
corner Frequency
Frequency) Utility line
Phase Locked Loop filter
corner Frequency
Hz
40.0
0.0 – 150.0
N N
LS PWM FREQ
(Line Side PWM
Frequency) Converter
PWM Freq
Frequency) Converter
PWM Freq
kHz
10.0
2.5 – 16.0
N N
Table 8: Line Side Power Convert A5
46