Power Supply Modules
3-25
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
A5E00069467-07
Technical Specifications of the PS 407 10A and the PS 407 10A R
Dimensions, Weight, and Cable Cross-Sections
Dimensions WxHxD (mm)
Weight
Cable cross-section
50x290x217
1.36 kg
3 x 1.5 mm
2
(litz wire
with wire end ferrule
with insulating collar;
use only flexible
sheath cable)
with insulating collar;
use only flexible
sheath cable)
Cable diameter
3 to 9 mm
Input Rating
Input voltage
•
Rated value
•
Permitted range
110/230 VDC
120/230 VAC
120/230 VAC
88 to 300 VDC,
85 to 264 VAC
(long-range input)
85 to 264 VAC
(long-range input)
System frequency
•
Rated value
•
Permitted range
50 / 60 Hz
47 to 63 Hz
Rated input current
•
At 120 VAC
•
At 110 VDC
•
At 230 VAC
•
At 230 VDC
1.2 A (0.9 A*)
1.2 A (1.0 A*)
0.6 A (0.5 A*)
0.6 A (0.5 A*)
Starting current inrush
•
At 230 VAC
Peak value 230 A,
half-value width 200
half-value width 200
µ
s
Peak value 63 A*,
half-value width 1 ms*
half-value width 1 ms*
•
At 300 VDC
Peak value 230 A,
half-value width 200
half-value width 200
µ
s
Peak value 58 A*,
half-value width 1 ms
half-value width 1 ms
Leakage current
< 3.5 mA
Overvoltage resistance
In accordance with DIN
VDE 0160, curve W2
VDE 0160, curve W2
* PS 407 10A:
As of version 5
* PS 407 10A R:
As of version 7
Output Variables
Output voltages
•
Rated values
5.1 VDC /24 VDC
Output currents
•
Rated values
5 VDC: 10 A
24 VDC: 1.0 A
Max. residual ripple
5 VDC: 50 mV
SS
24 VDC: 200 mV
SS
Max. switching peaks
5 VDC: 150 mV
S
24 VDC: 500 mV
S
Idle conditions
5 VDC: 200 mA base
load required
load required
24 VDC: Idling-proof
(no base load required)
(no base load required)
Other Parameters
Protection class in accordance
with IEC 60536
with IEC 60536
I, with protective
grounding conductor
grounding conductor
Overvoltage category
II
Pollution severity
2
Rated voltage U
e
0 < U
e
≤
50 V
150 V < U
e
≤
300 V
Test Voltage
700 VDC
(secondary <–> PE)
(secondary <–> PE)
2300 VDC
(primary <–> PE)
(primary <–> PE)
Buffering of power failures:
> 20 ms
Complies with the
NAMUR
recommendation NE
21 of August 1998 at a
repeat rate of 1 s
Complies with the
NAMUR
recommendation NE
21 of August 1998 at a
repeat rate of 1 s
Power input
105 W*
Power loss
29.7 W
Backup current
Max. 100
µ
A at power
off
Backup batteries (optional)
2 x Lithium AA, 3.6 V /
1.9 Ah
1.9 Ah
Protective separation
to IEC 61131-2
to IEC 61131-2
Yes