Siemens M7-400 사용자 설명서

다운로드
페이지 638
Digital Modules
4-55
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
Technical Specifications of the SM 421; DI 16 
x
 120/230 VUC
Dimensions and Weight
Dimensions W 
 
 H 
 
 D
(in millimeters)
25 
 
 290 
 
 210
Weight
Approx. 650 g
Data for Specific Module
Number of inputs
16
Length of cable
Unshielded
Shielded
600 m
1000 m
Voltages, Currents, Potentials
Power rated voltage of the
electronics L+
None
Number of inputs
that can be triggered
simultaneously
16
Isolation
Between channels and
backplane bus
Yes
Between the channels
Yes
In groups of
4
Permitted potential difference
Between M
internal
 and the
inputs
250 VAC
Between the inputs of the
different groups
500 VAC
Insulation resistance
4000 VAC
Current consumption
From the backplane bus
Max. 80 mA
Power dissipation of the
module
Typ. 12 W
Status, Interrupts, Diagnostics
Status display
Green LED per
channel
Interrupts
None
Diagnostic functions
None
Substitute value can be applied
No
Data for Selecting a Sensor 
Input voltage
Rated value
For signal “1”
120/230 VUC
 74 to 264 VAC
 80 to 264 VDC
–80 to –264 VDC
For signal “0”
0 to 40 VAC
–40 to +40 VDC
Frequency range
47 to 63 Hz
Input current
At signal ”1” (120 V)
Typ. 10 mA AC
Typ. 1.8 mA DC
At signal ”1” (230 V)
Typ. 14 mA AC
Typ. 2 mA DC
At signal “0”
0 to 6 mA AC
0 to 2 mA DC
Input delay
At “0” to “1”
Max. 20 ms AC
Max. 15 ms DC
At “1” to “0”
Max. 30 ms AC
Max. 25 ms DC
Input characteristic curve
To IEC 61131; 
type 2
Connection of two-wire BEROs
Permitted bias current
Possible
Max. 5 mA AC