Toshiba XLTR-200 사용자 설명서

다운로드
페이지 99
 
  
46
Note that this coil-to-register/bit relationship holds true regardless of whether or 
not holding register #3 is assigned to a point.  If holding register #3 is not 
assigned to a point, then a Modbus exception will be returned.  Either way, coil 
#34 will always access holding register #3, bit #1. 
 
 
13.1.2  Modbus RTU Slave 
• 
Broadcast (for functions 5, 6, 15 and 16) is supported. 
 
• 
Network characteristics selections 
o  Baud rate: 2400 / 4800 / 9600 / 19200 / 38400 bps 
o  Parity: odd / even / none (1 stop bit) / none (2 stop bits) 
 
 
13.1.3  Modbus RTU Master 
• 
Supported Modbus master functions are indicated in Table 2.  These 
functions are automatically invoked by the gateway in response to point 
read or write requests.  The specific read or write function code used 
depends on the point’s assigned configuration. 
 
Table 2: Supported Modbus Master Functions 
Function Code 
Function 
Read multiple registers 
Read input registers 
Write single register 
16 
Write multiple registers 
 
 
• 
The slave response timeout (in seconds) is assigned via the designated 
port’s “Timeout” selection.  If “0” is chosen (an invalid timeout time), the 
gateway will use a 2s timeout by default. 
 
• 
Network characteristics selections 
o  Baud rate: 2400 / 4800 / 9600 / 19200 / 38400 bps 
o  Parity: odd / even / none (1 stop bit) / none (2 stop bits) 
 
• 
Note that various manufacturers will document their Modbus slave 
products in different ways.  In particular, according to the Modbus 
specification, registers have two different indices at which they can be 
referenced: their “known as” value (which starts at number 1) and their 
“addressed as” value (which is always 1 less than the “known as” value).  
The “known as” value is typically the number that is presented for human 
entry or consumption, while the “addressed as” value is the number that 
appears “on the wire” when the Modbus packet is sent from master to