13.6.3  Subpoint Details 
This section gives a brief overview of each subpoint, including any notable 
behavior or settings.  Further information may be obtained by referring to 
applicable Mitsubishi ASD documentation.  
 
1. ADDRESS 
This is the FLN address of the drive.  It can be changed via FLN or via the 
gateway’s serial console. 
 
2. APPLICATION 
This is the Application ID for FLN on the A500/F700 drives. This ID is assigned 
by Siemens for each unique application, and correlates directly to a particular 
point list approved at the time of release.  The Application ID assigned to the 
A500/F700 drives is 2750. 
 
3. FREQ OUTPUT 
The output frequency of the drive in Hertz.  Corresponds to drive parameter 
1003. 
 
4. OUTPUT CUR 
The output current of the drive in Amps.  Corresponds to drive parameter 1004. 
 
5. OUTPUT VOLT 
The output voltage of the drive in Volts.  Corresponds to drive parameter 1005. 
 
6. SPECIAL MON 
This is the point which allows monitoring of a selected special monitor item.  
The meaning of the value, scaling and engineering units displayed here 
depends on the setting of the MON SELECT item (point #7).  Corresponds to 
drive parameter 1006. 
 
7. MON SELECT 
This point allows a selection of data codes to be written to it.  Each designated 
code corresponds to a particular drive status item that will then be reflected in 
the SPECIAL MON item (point #6).  Please refer to the applicable Mitsubishi 
documentation for a list of available codes.  Corresponds to drive parameter 
1007. 
 
8. ACCEL TIME 
Acceleration time in seconds.  Corresponds to drive parameter 7. 
 
9. DECEL TIME 
Deceleration time in seconds.  Corresponds to drive parameter 8. 
 
10. CMD FWD.STOP 
Commands the drive to run forward or stop.  Note that commanding this point is 
effective only when the drive is configured for network start/stop control.  
Corresponds to drive command parameter 1014, bit #1.