Toshiba XLTR-200 사용자 설명서

다운로드
페이지 99
 
  
80
Parameter 
Function / Title Bank 
Mask 
Adjustment Range 
Multiplier 
0133 
STALL PROTECTION 
ENABLE 
0 / 1 
0040 
0000: ON 
(0) 
0040: OFF 
(1) 
 
0134 
STALL 
PROTECTION 
CURRENT LEVEL 
0 / 1 
00FF 
000A 
∼ 00D7 (10 ∼ 215) 
0135 
UNDERVOLTAGE TRIP 
SELECTION 
0 / 1 
0080 
0000: Trip disabled 
(0) 
0080: Trip (during run) 
(1) 
 
0136 
UNDERVOLTAGE DETECT 
TIME 
0 / 1 
FFFF 
0000 
∼ 03E8 (0.00 ∼ 10.00) 
0.01 
0137 
LOW CURRENT DETECT 
SELECTION 
0 / 1 
0008 
0000: Trip disabled 
(0) 
0008: Trip on detection 
(1) 
 
0138 
LOW CURRENT DETECT 
LEVEL 
0 / 1 
00FF 
0000 
∼ 0064 (0 ∼ 100) 
0139 
LOW CURRENT 
DETECTION TIME 
0 / 1 
00FF 
0000 
∼ 00FF (0 ∼ 255) 
0140 
OUTPUT SHORT-
CIRCUIT DETECTION 
SELECT 
0 / 1 
0003 
0000:  Standard motor 
(0) 
0001: High-speed 
motor 
(1) 
0002:  Positioning use (standard 
motor) (2) 
0003:  Positioning use (high-speed 
motor) (3) 
 
0141 
OVERTORQUE TRIP 
SELECTION 
0 / 1 
0040 
0000: Trip disabled 
(0) 
0040: Trip enabled 
(1) 
 
0142 
OVERTORQUE TRIP 
LEVEL 
0 / 1 
00FF 
0000 
∼ 00C8 (0 ∼ 200) 
0143 
FAULT TRIP EEPROM 
SAVE ENABLE 
0 / 1 
0002 
0000:  Data cleared when  powered 
OFF (0) 
0002:  Data retained when powered 
OFF (1) 
 
0144 
COOLING FAN CONTROL 
SELECTION 
0 / 1 
0004 
0000:  Automatic (temperature 
detection) (0) 
0004: Always 
ON 
(1) 
 
0145 
CUMULATIVE RUN 
TIMER ALARM SETTING 
0 / 1 
FFFF 
0000 
∼ C34B (0.00 ∼ 999.90) 
0.02