User’s Manual   
69
 
2. Expanded Functions 
 
 
 
  
 
Ethernet 
 
 
 
 
IP address = 133.113.98.10 
 
  
T3H 
T3H 
  
(self-station) 
(target-station) 
 
 
F5000  
D4000  
F5001  
D4001  
   
   
   
   
F5199  
D4199  
 
 
When R0030 is ON, 200 words data starting with D4000 of the T3H on which EN311 (IP address = 
133.113.98.10) is installed, is read and stored in F5000 and after. 
When the operation is completed, the status is set in RW060 and instruction output comes ON. 
 
 
Note 
 
• 
Keep the input ON until the output comes ON. 
 
• 
This instruction becomes error complete in the following cases. (ERF = S0051 is set to ON) 
(1)  Target station No. is invalid. (for S20LP) 
(2)  Invalid register designation. (In case of T and C registers, T 
 T and C 
 C is only possible) 
(3)  Source/destination register address range is out of valid range. 
(4)  Destination register is write-protected. 
(5)  Response time-out is occurred. 
(6)  If expanded F register is designated; 
   
- when MMR setting is not made. 
   
- when IC card is not installed. 
   
- when IC card is used to store program. 
   
- when IC card is write-protected. (for destination) 
 
• 
By using SW067, self-station’s register write-protect is available. 
 
 
F            9 8 7 6 5 4 3 2 1 0 
SW067  SW 
 
RW 
LW 
YW 
 
 
 
0:  Write enable 
 
 
1:  Write protect 
 
 
• 
Resetting the status register (operand B) is necessary at the first scan. 
 
• 
When using the TOSLINE-S20LP or Ethernet module (EN311), read the manual for these network 
modules. 
 
Both F register in CPU and 
expanded F register in IC card