1.  Overview 
 
 
The Modbus module (ML11) is used to connect T2E, T2N, or EX100 PLCs to a Modbus 
Master. The addition of the EX10-MML11 (MODBUS Module) allows the T2E, T2N or  EX100 
PLC to communicate via standard MODBUS RTU protocol.  This allows quick and easy 
access to the PLC registers by a standard MODBUS Master. 
 
 
Using the ML11 Modbus module any Modbus Master can read the status of registers in the 
PLC and write to registers in the PLC.  This allows the Modbus Master to know the status of 
inputs to the PLC (both digital and analog) and to control the outputs of the PLC (also both 
digital and analog). 
 
 
The ML11 Modbus module cannot be a Modbus master, only a modbus slave.  It has one 
RS485 port for connection to the Modbus master.  The preferred location of the EX10-MML11 
is next to the CPU.  However, the module may be located in any slot to the right of the CPU. 
 
The CPU module can be any of the following:             
EX10-MPU11    
EX100 CPU, now obsolete 
EX10-MPU12A  
EX100 CPU, now obsolete 
TPU215—S 
 
T2 CPU now obsolete 
TPU224--S 
 
T2 CPU, now obsolete 
TPU234E-S 
 
T2E CPU  (replaces all obsolete CPUs) 
TPU215N-S 
 
T2N CPU, basic 
TPU235N-S 
 
T2N CPU, with Ethernet 
TPU245N-S 
 
T2N CPU, with Ethernet and Tosline S20 
 
 
 
 
The ML11 Modbus module is also used to connect a T2 or EX100 PLC into the Toshiba 
ECBUS.  The ECBUS allows the PLCs to share data with Toshiba’s EC300 series loop 
controllers.  The ECBUS is a LAN (local area network) which allows multiple EC300s and 
T2/EX100 PLCs to share data.  For more information on the ECBUS, please refer to ECBUS 
Transmission Interface Manual, see 
Additional References