CHAPTER 5 DESCRIPTION OF PARAMETER SETTINGS 
a
: This parameter can be set during operation. 
5.1 Group 0: AC Drive Status Parameters  
 Group 0 is read-only. 
00 - 00 
Software Version 
    Factory setting:  Read Only
  This parameter displays the software version of AC drive. 
00 - 01 
AC Drive Status Indication 1 
    Factory setting:  Read Only
  This parameter displays the AC drive status.  
Code 
AC Drive Status 
Explanation 
00  No fault occurred 
 
01 oc 
over 
current 
02 ov 
over 
voltage 
03 oH 
over 
temperature 
04 oL 
overload 
05 oL1 
electronic 
thermal 
relay 
06  EF (external fault) 
EF-DCM is closed  
07  occ (AC drive IGBT fault ) 
IGBT short circuit protection 
08  cF3 (CPU failure) 
Abnormal A/D reading during self-check 
09  HPF (hardware protection failure) 
Hardware protection function activated 
during self-check. 
10  ocA (over current during acceleration) 
Output current exceeds protection level 
during acceleration 
11  ocd (over current during deceleration) 
Output current exceeds protection level 
during deceleration 
12  ocn (over current during steady state 
operation) 
Output current exceeds protection level 
during steady state operation. 
13  GFF (ground fault) 
Ground fault protection feature activated 
14  Lv (under voltage) 
Low input voltage 
15  cF1  
EEPROM input data is abnormal 
16  cF2  
EEPROM output data is abnormal 
17  bb (base block) 
BB is set and activated  
18  oL2 (motor over load 2) 
Output current exceeds rated motor current
19 Reserved 
 
20  codE 
software or password protection 
21  EF1 (external emergency stop) 
EF1 (a multifunction-DCM is enabled) 
22  PHL (phase loss) 
Input power lacks phase. 
3-phase input power is unbalance and 
exceeds specification.  
23  Lc (Low Current) 
Low current detection during operation. 
24  FbL(Feedback Loss) 
Feedback signal is abnormal. 
25 Reserved