5.4 Group 3: Output Function Parameters 
03 - 00 
Multi-function Output terminal 1 
Factory Setting: 00
03 - 01 
Multi-function Output terminal 2 
Factory Setting: 00
03 - 02 
Multi-function Output terminal 3 
Factory Setting: 00
03 - 03 
Multi-function Output terminal 4 
Factory Setting: 00
03 - 04 
Multi-function Output terminal 5 
Factory Setting: 00 
03 - 05 
Multi-function Output terminal 6 
Factory Setting: 00 
03 - 06 
Multi-function Output terminal 7 
Factory Setting: 00 
03 - 07 
Multi-function Output terminal 8 
Factory Setting: 00 
 Settings 
00-33 
 
Setting Functions 
Descriptions 
00 No 
function 
 
01 Motor 
No. 
02 Motor 
No. 
03 Motor 
No. 
04 Motor 
No. 
05 Motor 
No. 
06 Motor 
No. 
07 Motor 
No. 
08 Motor 
No. 
When starting circulative control, AC drive will 
automatic set this parameter by 11-01 to 11-03.
09 Auxiliary 
output 
10 Auxiliary 
output 
11 Auxiliary 
output 
12 Auxiliary 
output 
13 Auxiliary 
output 
14 Auxiliary 
output 
15 Auxiliary 
output 
Parameter value 09 to 15 program 
Multi-Function Output Terminals 
(Pr.03-00~Pr.03-07) to correspond with the AC 
drive multi-function input terminals, Pr.04-00 to 
04-07(settings 20~26). 
16 Indication 
during 
operation 
The 
corresponding output will be closed during 
operation (including DC brake time).  
17 Master 
frequency 
attained  
The corresponding output will be closed when 
output frequency reaches master frequency 
command.  
18 
Zero Speed (including shutdown) 
The corresponding output will be closed when 
the AC drive has no output voltage signal.  
19 
Over-torque  
The corresponding output relay will be closed 
when the AC drives output current exceeds the 
over-torque detection level 06-04.  
20 
External Fault 
The corresponding output will be closed when 
the EF is enabled.  (Pr. 4-00 to 4-07)