Delta Electronics VFD-VL 사용자 설명서

다운로드
페이지 251
Chapter 1 Introduction| 
1-6 
 Revision Nov. 2008, VLE1, SW V1.03
1.2 Preparation for Installation and Wiring
 
1.2.1 Ambient Conditions 
Install the AC motor drive in an environment with the following conditions: 
Air Temperature: 
-10 ~ +45°C (14 ~ 113°F) 
Relative Humidity:
<90%, no condensation allowed 
Atmosphere 
pressure: 
86 ~ 106 kPa 
Installation Site 
Altitude: 
<1000m 
Operation 
Vibration: 
<20Hz: 9.80 m/s
2
 (1G) max 
20 ~ 50Hz: 5.88 m/s
2
 (0.6G) max 
Temperature: -20°C 
+60°C (-4°F ~ 140°F) 
Relative Humidity:
<90%, no condensation allowed 
Atmosphere 
pressure: 
86 ~ 106 kPa 
Storage 
Transportation 
Vibration: 
<20Hz: 9.80 m/s
2
 (1G) max 
20 ~ 50Hz: 5.88 m/s
2
 (0.6G) max 
Pollution Degree  2: good for a factory type environment. 
 
Minimum Mounting Clearances 
 
H
Air Flow
H
W
W
 
 
HP 
mm (inch) 
mm (inch) 
7.5-20HP 
75 (3) 
175 (7) 
25-75HP 
75 (3) 
200 (8) 
100HP 
75 (3) 
250 (10)