                                                             Chapter 6 Fault Code Information and Maintenance| 
Revision Nov. 2008, VLE1, SW V1.03                                                                                                                       6-11
 
6.2 Maintenance and Inspections 
Before the check-up, always turn off the AC input power and remove the cover. Wait at least 10 
minutes after all display lamps have gone out, and then confirm that the capacitors have fully 
discharged by measuring the voltage between DC+ and DC-. The voltage between DC+ and DC-
should be less than 25VDC. 
 
„
 
Ambient environment 
Maintenance 
Period 
Check Items 
Methods and Criterion 
Daily
Half 
Year
One 
Year
Check the ambient temperature, 
humidity, vibration and see if 
there are any dust, gas, oil or 
water drops 
Visual inspection and measurement 
with equipment with standard 
specification 
{
 
 
If there are any dangerous 
objects 
Visual inspection 
{
 
 
 
„
 
Voltage 
Maintenance 
Period 
Check Items 
Methods and Criterion 
Daily
Half 
Year
One 
Year
Check if the voltage of main 
circuit and control circuit is 
correct 
Measure with multimeter with standard 
specification 
{
 
 
 
„
 
Keypad
 
Maintenance 
Period 
Check Items 
Methods and Criterion 
Daily
Half 
Year
One 
Year
Is the display clear for reading 
Visual inspection 
{
 
 
Any missing characters 
Visual inspection 
{