Appendix B Accessories|
B-12
Revision Nov. 2008, VLE1, SW V1.03
460V, 50/60Hz, 3-Phase
Inductance (mH)
kW HP
Fundamental
Amps
Max.
continuous
Amps
3% impedance
5% impedance
5.5
7.5
18 27 1.5
2.5
7.5
10
18 27 1.5
2.5
11
15
25 37.5 1.2
2
15
20
35 52.5 0.8
1.2
18.5
25
45 67.5 0.7
1.2
22
30
45 67.5 0.7
1.2
30
40 80
120
0.4
0.7
37
50 80
120
0.4
0.7
45
60 100
150
0.3
0.45
55
75 130
195
0.2
0.3
75
100 160
240
0.15
0.23
B.4.3 Applications for AC Reactor
Connected in input circuit
Application 1
Question
When more than one AC motor drive is
connected to the same power, one of them
is ON during operation.
is ON during operation.
When applying to one of the AC motor
drive,
the charge current of capacity may cause
voltage ripple. The AC motor drive may
damage when over current occurs during
operation.
the charge current of capacity may cause
voltage ripple. The AC motor drive may
damage when over current occurs during
operation.