                                                                                                      Chapter 3 Operation and Start Up|  
Revision Nov. 2008, VLE1, SW V1.03                                                                                                                       3-5
 
3.3.2 Explanations for the Auto-tuning Steps 
3.3.2.1 Step 1 
Basic parameters settings 
„  Make sure that Pr.00-00 (identity code of the AC motor drive) corresponds with the 
nameplate indicated on the AC motor drive. 
„  Make sure that all parameters are reset to factory setting (Pr.00-02 is set to 9 or 10). 
Pr.00-02 
Parameter Reset 
0: No function 
1: Read only 
8: Keypad lock 
9: All parameters are reset to factory settings (50Hz, 
220V/380V)  
10: All parameters are reset to factory settings (60Hz, 
220V/440V) 
„  Source of the Master Frequency Command: users can set by themselves (Pr.00-14) 
Pr.00-14 
Source of the 
Master Frequency 
Command 
1: RS-485 serial communication or digital keypad 
(KPVL-CC01) 
2: External analog input (Pr. 03-00) 
3: Digital terminals input 
„  Source of the Operation Command: users can set by themselves (Pr.00-15) 
Pr.00-15 
Source of the 
Operation 
Command 
1: External terminals 
2: RS-485 serial communication or digital keypad 
(KPVL-CC01) 
„ MI/MO external terminals settings: 
Refer to Pr.02-01~02-08 for setting the external input terminals MI1~MI8. 
NOTE: The factory setting of Pr.02-08 is 40 (Enable drive function). Please disable this 
function if you don’t need to use this function. 
Settings of Pr.02-
01~02-08 
 
0: no function 
1: multi-step speed command 1 
2: multi-step speed command 2 
3: multi-step speed command 3 
4: multi-step speed command 4 
5: Reset 
6: JOG command 
7: acceleration/deceleration speed inhibit 
8: the 1st, 2nd acceleration/deceleration time selection 
9: the 3rd, 4th acceleration/deceleration time selection 
10: EF input (07-28) 
11: Reserved 
12: Stop output  
13: Disable auto accel./decel. function