                                                                                                      Chapter 3 Operation and Start Up|  
Revision Nov. 2008, VLE1, SW V1.03                                                                                                                       3-13
 
3.3.2.5 Step 5 
Trial run 
This step is used to trial run after finishing the settings of Step 1 to Step 4 to check if it runs 
normally after executing the inspection with the loaded motor. At the same time, please also 
check if the operations of multi-function output terminals is normal, such as the action of 
the brake release and electromagnetic valve correspond to the host controller. 
It needs to check the switch between each step speed, current value, the noise in the 
carriage and noise source during operation. 
 
3.3.2.6 Step 6 
Elevator tuning 
1. 
Setting Pr. 11-00 to bit 0=1 
Pr.11-00 
System control
 
Bit 0=0: disable 
Bit 0=1: ASR Auto tuning, PDFF enable 
Bit 7=1: When position control is enabled, it doesn’t need to 
set Pr.07-02 (DC Brake Current Level) 
Bit 15=0: when power is applied, it will detect the position of 
magnetic field again 
Bit 15=1: when power is applied, it will start from the magnetic 
field position of previous power failure 
2. 
Smooth test for general operation 
„  Adjust the setting of Pr.11-05 
Pr.11-05 
Inertial Ratio
 
1~300% 
„  Adjust the settings of Pr.11-06 to Pr.11-08 
Zero-speed Bandwidth 
0~40Hz 
Low-speed Bandwidth 
0~40Hz 
Settings of Pr.11-
06 to Pr.11-08 
High-speed Bandwidth 
0~40Hz 
3. 
Start-up adjustment (only for PM motor) 
„  Control by the zero-speed position 
Setting Pr.11-00, 10-19, 10-22, 10-23, 02-29 and 10-24 
Pr.11-00 
System control
 
Bit 0=0: disable 
Bit 0=1: ASR Auto tuning, PDFF enable 
Bit 7=1: When position control is enabled, it doesn’t need 
to set Pr.07-02 (DC Brake Current Level) 
Bit 15=0: when power is applied, it will detect the position 
of magnetic field again 
Bit 15=1: when power is applied, it will start from the 
magnetic field position of previous power failure