Chapter 2 Installation and Wiring| 
2-10 
 Revision August 2008, 03VE, SW V2.04
Frame D 
3
V/T2 W/T3
R/L1
DC 
DC  + 
(  ) 
(  ) 
POWER 
S/L2 T/L3
-
+2
+1
MOTOR
IM
 
 
 
Main circuit terminals 
R/L1, S/L2, T/L3, U/T1, V/T2, W/T3, 
, +1, +2, - 
 
Models 
Wire 
Torque
Wire Type
VFD110V23A-2
VFD110V43A-2
VFD150V43A-2
VFD150V23A-2
VFD185V23A-2
VFD185V43A-2
VFD220V43A-2
VFD220V23A-2
8-2 AWG  
(8.4-33.6mm
2
30kgf-cm
(26in-lbf)
Stranded 
copper only, 
75
 o
 
Frame E 
W/T3
S/L2
R/L1
T/L3
+2
+1
U/T1 V/T2
(173in-lbf)
Screw Torque:
200kgf-cm
POWER 
IM
MOTOR
3
POWER 
ALARM
CHARGE
 
Main circuit terminals 
R/L1, S/L2, T/L3, U/T1, V/T2, W/T3, 
, +1, +2, - 
 
Models 
Wire 
Torque 
Wire Type
VFD300V43A-2
VFD370V43A-2
VFD450V43A-2
57kgf-cm
(49in-lbf)
VFD300V23A-2
VFD370V23A-2
VFD550V43C-2
VFD750V43C-2
4-2 AWG  
(21.2-33.6mm
2
)
200kgf-cm
(173in-lbf)
Stranded 
copper 
only, 75
 o
C
 
NOTE
 
To connect 6 AWG (13.3 mm
2
) wires, use Recognized Ring Terminals 
 
2.4 Control Terminals 
Circuit diagram for digital inputs (SINK current 16mA.)