1 Power Supply 
Locate the power supply at the end, middle, or anywhere along the cable, as illustrated in 
the following figure. 
 
 
 
Figure 12: 1 Power Supply 
Grounding the Interconnect System 
You must ground the QCPort system at only one location. 
 
 Warning 
If you use more than one power supply, all of them should be attached to the same 
earth ground. 
 
Ground the G conductor at only one place at the power supply that is closest to the 
physical center of the QCPort system to maximize the performance and minimize the 
effect of outside noise.  
To ground QCPort: 
•  Connect the G wire to earth ground using a 1 in (0.25 mm) copper braid or a #8 
AWG wire up to 10 ft (3 m) maximum in length. 
•  Use the same wire to connect the power tap to earth ground. 
Power 
Supply 
Device 
Device 
Device 
Biasing resistor 
Biasing resistor