Using the Sizing Calculation 
The following examples use the sizing calculation to determine if the power supply is 
placed correctly in the system and if the power supply is large enough for the application.   
Example 1 End Connected Power Supply  
 
 
 
 
 
1.  Sum up all the currents (QCPort Interconnect system) 
=0.1 + 1.1 + 0.3 = 1.5A (too much for Interconnect) 
The supply will have to be relocated. 
Example 2 End Connected Power Supply  
 
 
 
 
 
1.  Sum up the currents (QCPort Interconnect system) 
=0.1 + 0.4 + 0.3 = 0.8 A (OK since 10 feet allows 1.0A) 
2.  Find the voltages for each node using the equation for Long Run. 
SUM {[(L
n
 x (0.105)) + (N
t
 x (0.005))] x I
n
 } <= 4.65V 
Device 1 [(20 x (0.105)) + (1 x (0.005))] x 0.1 0.21V 
Device 2 [(30 x (0.105))+ (2 x (0.005))] x 0.4 1.26V 
Device 3 [(40 x (0.105)) + (3 x (0.005))] x 0.3 1.26V 
3.  Add each Devices voltage together to find the total voltage. 
0.21 + 1.26 + 1.26 = 2.73(OK) 
Results 
Since the total voltage does not exceed 4.65V, the system will operate properly. 
PS 
D2 
0.4A
D3 
0.3A 
D1 
0.1A
10 foot 
10 foot
10 foot 
10 foot 
10 foot
PS 
D2 
1.1A
D3 
0.3A 
D1 
0.1A
1 foot 
1 foot 
1 foot 
1 foot 
1 foot