B.1 Command Set 
The full DCON protocol command sets for i-8000 series’ can be found in 
 
CD:\Napdos\DCON\IO_Module\ 
 
Frequently used Command table reference: 
 
Command Command 
Description 
$AAM 
Reads the Module Name 
$AAF 
Reads the Firmware Version 
#AASi 
Reads the analog input or counter / frequency values for all channels 
of a specified slot 
#AASiCj 
Reads the analog input or counter/frequency module data from 
specified slot and the specified channel in the I-8000 unit. 
#AASiCj(data) 
Sets the analog voltage output module data from the specified slot 
and channel in the I-8000 unit. The data format is in engineering units 
only. 
#AASi6 
Read Digital input and output status at specified slot 
#AASi00(data)  Sets the multiple Digital output of a specified slot 
# AASiBjDS 
Sets the single Digital output of a specified slot 
 