Operating Characteristics - Controller Modes 
110 
  HC900 Hybrid Controller Installation and User Guide 
Revision 5 
  
9/03 
Controller Modes 
The HC900 Controller includes three operating modes.  The purpose of each mode is described 
immediately below, and salient characteristics of each are described in Table 19.  The functions of the 
Mode Switch are described in Table 20, and the procedures that the controller performs in transitions 
between modes are described in Table 21. 
PROGRAM Mode 
In the PROGRAM Mode, active control processing is suspended.  This mode is used for safe execution of 
utility functions such as configuration download and calibration of analog inputs and outputs.  
All outputs are Off. 
RUN Mode 
The Run Mode is used for normal operation of the controller; that is, for running the control configuration 
that was previously downloaded.  Configuration download and other utility functions can be performed in 
this mode.  See the Hybrid Control Designer User Guide for precautions, restrictions, and procedures. 
OFFLINE Mode 
The OFFLINE Mode can be entered only from the RUN Mode, and is intended primarily for performing AI 
calibration.   
 
 
 
Because Function Blocks are not processed and outputs are Frozen in this mode, inputs (that 
is, process values) can vary from the values that existed when the OFFLINE Mode was 
entered. 
Before entering the OFFLINE Mode:  
•  KNOW all potential consequences of suspending control action.. 
•  PLAN for all operator actions required to preclude adverse consequences while processing 
is suspended, and when resuming control processing. 
•  EXECUTE prudent control actions (such as placing all control loop in the Manual Mode). 
Failure to comply with these instructions may result in product damage.