Honeywell HC900 사용자 설명서

다운로드
페이지 228
Removal and Replacement Procedures - Safety Considerations - PLAN AHEAD! 
Revision 5 
  HC900 Hybrid Controller Installation and User Guide 
153 
9/03  
Battery Installation Procedures 
Table 36 - Installing Backup Battery (CPU not initialized) 
Step Action 
1. 
 
Improper application of site power can cause damage to equipment. 
Ensure that the controller rack is ready and safe for application of AC power. 
2. 
Apply site AC power to the Power Supply that is associated with the controller Module..  
3. 
Open the plastic door at the top of the Controller 
Module. 
Press the latch on the battery cover to the right to 
release the battery holder, and use the molded-in 
extension on the battery holder to extract the 
holder. 
Note the orientation of the battery-holder assembly 
(battery toward the left). 
 
 
4.  
The battery is retained in the holder by spring 
tension of the plastic holder itself. 
Insert the negative end of the battery into the back 
end of the holder, and press on the battery so that it 
snaps into the holder. 
To ensure that the battery is seated properly, rotate 
it in the holder, using finger or thumb pressure 
toward the positive (front) end of the battery. 
 
5. 
While maintaining proper orientation (battery toward the left), slide the battery holder into the 
slot in the Controller Module until it snaps into place.