Honeywell HC900 사용자 설명서
Appendix B Installation of Remote Termination Panels (RTPs) - Digital Input/Digital Output/Analog Output
194
HC900 Hybrid Controller Installation and User Guide
Revision 5
9/03
Digital Input/Digital Output/Analog Output
The DI/DO/AO-RTP is for use with the following modules:
See page
• 4-point Analog Output
• 16-point Contact Digital Input
• 16-point DC Digital Input
• 16-point AC Digital Input
• 16-point DC Digital Output
• 8-point AC Digital Output
4 Point Analog Output
Step Action
1
ATTENTION: RTP and cables are intended for permanent installation within their own enclosure.
Mount RTP cable assembly to HC900 Controller (Figure 60).
•
Remove appropriate key tabs from terminal block to allow mating with the module. See page 64.
•
Connect desired cable to AO module at controller. Choose from:
900RTC-L010 Remote Terminal Low Voltage Cable Assembly, 1.0 meters long
900RTC-L025 Remote Terminal Low Voltage Cable Assembly, 2.5 meters long.
900RTC-L050 Remote Terminal Low Voltage Cable Assembly, 5.0 meters long
900RTC-L010 Remote Terminal Low Voltage Cable Assembly, 1.0 meters long
900RTC-L025 Remote Terminal Low Voltage Cable Assembly, 2.5 meters long.
900RTC-L050 Remote Terminal Low Voltage Cable Assembly, 5.0 meters long
•
Install AO module label onto the module connector cover.
•
Connect shield drain wire to the grounding bars at the base of the HC900 rack. All field-wiring
shields must be grounded as described in the shield grounding section (page 60).
shields must be grounded as described in the shield grounding section (page 60).
2
Mount RTP to DIN rail.
•
Latch to rail. See page 205.
•
Connect cable to RTP
3
Set/verify jumper positions as shown for use with an analog output module.
Jumper open
Jumper closed
Jumper closed
SW1 is not used. Module RIUP is not affected by using the RTP.
See page 203 for RTP internal schematic.