Appendix B Installation of Remote Termination Panels (RTPs) - Digital Input/Digital Output/Analog Output 
194 
  HC900 Hybrid Controller Installation and User Guide 
Revision 5 
  
9/03 
Digital Input/Digital Output/Analog Output 
The DI/DO/AO-RTP is for use with the following modules: 
See page 
•  4-point Analog Output 
 
•  16-point Contact Digital Input 
 
•  16-point DC Digital Input 
 
•  16-point AC Digital Input 
 
•  16-point DC Digital Output 
 
•  8-point AC Digital Output 
 
 
4 Point Analog Output 
Step Action 
ATTENTION: RTP and cables are intended for permanent installation within their own enclosure. 
Mount RTP cable assembly to HC900 Controller (Figure 60). 
• 
Remove appropriate key tabs from terminal block to allow mating with the module. See page 64. 
• 
Connect desired cable to AO module at controller. Choose from: 
900RTC-L010  Remote Terminal Low Voltage Cable Assembly, 1.0 meters long 
900RTC-L025  Remote Terminal Low Voltage Cable Assembly, 2.5 meters long.  
900RTC-L050  Remote Terminal Low Voltage Cable Assembly, 5.0 meters long 
• 
Install AO module label onto the module connector cover. 
• 
Connect shield drain wire to the grounding bars at the base of the HC900 rack.  All field-wiring 
shields must be grounded as described in the shield grounding section (page 60). 
Mount RTP to DIN rail. 
• 
Latch to rail. See page 205. 
• 
Connect cable to RTP 
Set/verify jumper positions as shown for use with an analog output module. 
          
Jumper open
Jumper closed
 
SW1 is not used. Module RIUP is not affected by using the RTP. 
See page 203 for RTP internal schematic.