I/O Module Installation and Wiring - Remote Termination Panel (RTP) 
Revision 5 
  HC900 Hybrid Controller Installation and User Guide 
59 
9/03  
Remote Termination Panel (RTP) 
The optional Remote Termination Panel (RTP) provides an easy way to connect the HC900 controller to 
the field wiring.  The RTP integrates some of the typical externally connected components, reducing wiring 
and setup time.  It also minimizes the need for multiple wires under a single screw connection by 
expanding the connectivity of the shared terminals of the I/O modules. 
See Appendix B Installation of Remote Termination Panels (RTPs) for details. 
Terminal Block-to-Field (Signal) Wiring 
Although both of the two available terminal block styles can be used on all I/O module types, wiring 
methods vary with the module type and with the type of field devices connected to the terminal block.  The 
descriptions that follow provide details.   
Wiring can be routed through the terminal block at the top, at the bottom, or both.  Wiring should be fixed 
in place using wire ties at the slotted tabs that are molded in at top and bottom of each terminal block. 
Wiring Rules and Recommendations 
In general, stranded copper wire should be used for non-thermocouple electrical connections.  Twisted-pair 
wiring with shielded cable will improve noise immunity if wire routing is suspect.   
Wire Gage 
Observe all local codes when making power connections.  Unless local electrical codes dictate otherwise, 
the recommended minimum wire size for connections is given in Table 12. 
Table 12 - Minimum Recommended Wire Sizes 
Wire 
Gauge 
Wire Application 
14 
Earth ground to common power supply. 
14 to 16 
AC to power supply 
10 to 14 
Earth ground wire  
20 
DC current and voltage field wiring 
22 
DC current and voltage wiring in control room 
 
Routing and Securing Wires 
Typically, field wiring is routed to connections at a terminal panel near the controller and then from the 
terminal panel to the terminal blocks on the I/O modules.   
Whatever method of routing is used, wiring must be mechanically supported along its length, and must be 
protected from physical damage and electromagnetic (noise) interference.  (Refer to Installation Planning, 
Environmental Considerations, in this manual.)  
Also, all wires must be securely terminated, using appropriate wiring practices.